W3G500GN3307-LA1 

4.

 

CONNECTION AND START-UP

 

4.1

 

Mechanical system connection

 

CAUTION 

Cutting and crushing hazard when removing the 
device from the packaging. 

→  Carefully remove the device from its packaging by 

the fan housing. Strictly avoid shocks. 

→  Wear safety shoes and cut-resistant safety gloves. 

CAUTION 
Heavy load when unpacking the device 

Risk of physical injury such as back injuries. 
→ Two people should work together to remove the 

device from its packaging. 

 

Check the device for transport damage. Damaged devices 
must no longer be installed. 

 

Install the undamaged device according to your 
application. 

 

CAUTION 
Possible damage to the device 

If the device slips during installation, serious damage 
can result. 
→ Ensure that the device is securely positioned at its 
place of installation until all fastening screws have 
been tightened. 

4.2

 

Electrical connection 

DANGER 
Voltage on the device 

Electric shock 
→  Always install a protective earth first. 
→  Check the protective earth. 

DANGER 
Incorrect insulation 

Risk of fatal injury from electric shock 
→  Use only cables that meet the specified installation 

requirements for voltage, current, insulation material, 
load etc. 

→  Route cables such that they cannot be touched by 

any rotating parts. 

DANGER 

Electrical load (>50 µC) between mains wire and 
protective earth connection after switching of the 
supply when switching multiple devices in 
parallel. 

Electric shock, risk of injury 
→  Ensure sufficient protection against accidental 

contact. 
Before working on the electrical connection, 
disconnect the mains supply and PE. 

CAUTION

 

Voltage 

The fan is a built-in component and has no 
electrically isolating switch. 

→  Only connect the fan to circuits that can be switched 

off with an all-pole separating switch. 

→  When working on the fan, you must switch off the 

installation/machine in which the fan is installed and 
secure it from being switched on again. 

NOTE

 

Device malfunctions possible 

Route the control lines of the device separately from 

the supply line. 
→  Maintain the greatest possible clearance. 
 

Recommendation: clearance > 10 cm (separate 
cable routing) 

NOTE 
Water ingress into wires or cables 

Water ingress at the end of the cable can damage the 

device. 

→  Make sure the end of the cable is connected in a 

dry environment. 

→  The IP protection is guaranteed only if the 

provided cable glands are installed. 

Only connect the device to circuits that can be 
switched off with an all-pole disconnection switch. 
 

4.2.1

 

Requirements

 

 

Check whether the data on the name plate agree with the 
connection data.  

 

Before connecting the device, ensure that the power supply 
matches the device voltage. 

 

Only use cables designed for current indicated on the name 
plate. For determining the cross-section, follow the basic 
principles in accordance with EN 61800-5-1. The protective 
earth must have a cross-section equal to or greater than 
that of the phase conductor.  
We recommend the use of 105°C cables. Ensure that the 
minimum cable cross-section is at least AWG26/0.13 mm². 

 

Earth wire contact resistance in accordance with EN 61800-5-1 

Compliance with the impedance specifications in accordance 
with EN 60335 for the protective earth circuit must be verified in 
the end application.  
Depending on the installation situation, it may be necessary to 
install an additional protective earthing conductor via the 
additional protective earth connection point available on the 
device. 

4.2.2

 

Supply connection and fuses protection

 

Assignment of supply cable cross-sections and their fuses (line 
protection only, no equipment protection). 

Nominal 
voltage 

Fuse 

 

Automatic 
circuit 
breaker 

Cable 
cross-
section 

Cable 
cross-
section 

 

VDE 

UL 

VDE 

mm

2

 

*AWG 

3/PE AC 
380-480 
VAC 

16 A 

15 

C16A 

1.5  
2.5 

16 

*AWG = American Wire Gauge 

Содержание W3G500GN3307-LA1

Страница 1: ...disposal 12 1 SAFETY REGULATIONS AND INFORMATION Read these operating instructions carefully before starting work on the device Observe the following warnings to prevent malfunctions or danger to pers...

Страница 2: ...device immediately if you notice a missing or ineffective protective feature 1 6 Electromagnetic radiation Interference from electromagnetic radiation is possible e g in conjunction with open and clos...

Страница 3: ...resses that can occur Intended use also includes Use the device in power systems with earthed neutral TN TT power systems only Using the device only in stationary systems Performing all maintenance wo...

Страница 4: ...6400 NSW Fax 61 02 9827 6464 NZ Phone 64 09 525 0245 NZ Fax 64 09 525 0246 sales ebmpapst com au www ebmpapst com au W3G500GN3307 LA1 3 TECHNICAL DATA 3 1 Product drawing AIRFLOW DIRECTION All dimensi...

Страница 5: ...from the mains Over temperature protected electronics motor Line under voltage phase failure detection Touch current acc IEC 60990 measuring network Fig 4 TN system 3 5 mA Electrical leads Via termina...

Страница 6: ...is a built in component and has no electrically isolating switch Only connect the fan to circuits that can be switched off with an all pole separating switch When working on the fan you must switch o...

Страница 7: ...D protective devices cannot provide personal safety while operating the device When switching on the power supply of the device pulsed charge currents from the capacitors in the integrated EMC filter...

Страница 8: ...s not included in the scope of delivery into the terminal box First connect the PE protective earth Connect the lines to the corresponding terminals Use a screwdriver to do so When connecting ensure...

Страница 9: ...A max 250 VAC min 10 mA AC1 KL2 3 NO Floating status contact make for failure KL3 1 OUT Analogue output 0 10 VDC max 3 mA SELV Output of the current motor level 1 V corresponds to 10 level 10 V corres...

Страница 10: ...flammable materials are located close to the fan Before switching on check the device for visible external damage and make sure the devices are functional Check the air flow paths of the fan for forei...

Страница 11: ...cleaning Motor not turning Mechanical blockage Switch off isolate from supply and remove mechanical blockage Voltage faulty Check mains supply voltage restore power supply Important The error message...