W3G500GN3307-LA1 

6.

 

MAINTENANCE, MALFUNCTIONS, POSSIBLE CAUSES 
AND REMEDIES 

Do not perform any repairs on your device. Return the device to 
ebm-papst A&NZ for repair or replacement. 

WARNING 
Live terminals and connections have voltage 
even with a device that is switched off 

Electric shock 

→  Wait five minutes after disconnecting the voltage 

at all poles before opening the device. 

CAUTION 
If control voltage or a speed set value is applied, 
the motor will restart automatically, e.g. after a 
power failure. 

Risk of injury 

→  Keep out of the device danger zone. 
→  When working on the device, switch off the line 

voltage and ensure that it cannot be switched 
back on. 

→  Wait until the device stops. 
→  After working on the device, remove any used 

tools or other objects from the device. 

If the device remains out of use for some time, e.g. 
when in storage, we recommend switching the device 
on for at least two hours to allow any condensate to 
evaporate and to move the bearings. 

Malfunction/fault  Possible 

cause 

Possible remedy 

Impeller not 
running 
smoothly 

Imbalance in 
rotating parts 

Clean the device; 
replace it if imbalance 
persists after cleaning, 
replace the device. 
Make sure no weight 
clips are removed 
during cleaning. 

Motor not 
turning 

Mechanical 
blockage 

Switch off, isolate from 
supply, and remove 
mechanical blockage. 

 

Voltage faulty  Check mains supply 

voltage, restore power 
supply.  
Important! The error 
message resets 
automatically. Device 
restarts automatically 
without warning. 

 

Faulty 
connection 

Isolate from supply, 
correct connection, see 
connection diagram. 

 

Broken motor 
winding  

Replace device 

 

Thermal 
over-load 
protector 
activated 

Allow motor to cool off, 
locate and rectify cause 
of error, if necessary 
cancel restart lock-out. 

 

Insufficient 
cooling 

Improve cooling. Let 
the device cool down. 
To reset the error 
message, switch off the 

mains supply voltage 
for at least 25 s and 
then switch it on again. 
Alternatively, reset the 
error message by 
applying a control 
signal of <0.5 V to DIN1 
or by short Din1 to 
GND. 

 

Ambient 
temperature 
too high 

Reduce the ambient 
temperature. Let the 
device cool down. To 
reset the error 
message, switch off the 
mains supply voltage 
for at least 25 s and 
then switch it on again. 
Alternatively, reset the 
error message by 
applying a control 
signal of <0.5 V to DIN1 
or by short Din1 to 
GND. 

 

Unacceptable 
operating 
point (e.g. 
back 
pressure is 
too high) 

Correct the operating 
point. 
Let the device cool 
down. 
To reset the error 
message, switch off the 
mains supply voltage 
for at least 25 s and 
then switch it on again. 
Alternatively, reset the 
error message by 
applying a control 
signal of <0.5 V to DIN1 
or by short Din1 to 
GND. 

 

If you have any other problems, contact ebm-papst 
A&NZ 

6.1

 

Cleaning  

NOTE 
Damage to the device during cleaning 

Malfunctions possible 
→  Do not clean the device using a water jet or high-

pressure washer. 

→  Do not use any cleaners containing acids, bases 

or solvents. 

→  Do not use any pointed or sharp-edged objects to 

clean. 

Содержание W3G500GN3307-LA1

Страница 1: ...disposal 12 1 SAFETY REGULATIONS AND INFORMATION Read these operating instructions carefully before starting work on the device Observe the following warnings to prevent malfunctions or danger to pers...

Страница 2: ...device immediately if you notice a missing or ineffective protective feature 1 6 Electromagnetic radiation Interference from electromagnetic radiation is possible e g in conjunction with open and clos...

Страница 3: ...resses that can occur Intended use also includes Use the device in power systems with earthed neutral TN TT power systems only Using the device only in stationary systems Performing all maintenance wo...

Страница 4: ...6400 NSW Fax 61 02 9827 6464 NZ Phone 64 09 525 0245 NZ Fax 64 09 525 0246 sales ebmpapst com au www ebmpapst com au W3G500GN3307 LA1 3 TECHNICAL DATA 3 1 Product drawing AIRFLOW DIRECTION All dimensi...

Страница 5: ...from the mains Over temperature protected electronics motor Line under voltage phase failure detection Touch current acc IEC 60990 measuring network Fig 4 TN system 3 5 mA Electrical leads Via termina...

Страница 6: ...is a built in component and has no electrically isolating switch Only connect the fan to circuits that can be switched off with an all pole separating switch When working on the fan you must switch o...

Страница 7: ...D protective devices cannot provide personal safety while operating the device When switching on the power supply of the device pulsed charge currents from the capacitors in the integrated EMC filter...

Страница 8: ...s not included in the scope of delivery into the terminal box First connect the PE protective earth Connect the lines to the corresponding terminals Use a screwdriver to do so When connecting ensure...

Страница 9: ...A max 250 VAC min 10 mA AC1 KL2 3 NO Floating status contact make for failure KL3 1 OUT Analogue output 0 10 VDC max 3 mA SELV Output of the current motor level 1 V corresponds to 10 level 10 V corres...

Страница 10: ...flammable materials are located close to the fan Before switching on check the device for visible external damage and make sure the devices are functional Check the air flow paths of the fan for forei...

Страница 11: ...cleaning Motor not turning Mechanical blockage Switch off isolate from supply and remove mechanical blockage Voltage faulty Check mains supply voltage restore power supply Important The error message...

Страница 12: ...from the development stage ecological design technical safety and health protection are fixed criteria The following section contains recommendations for ecological disposal of the product and its com...

Отзывы: