Operating instructions

K3GA00-PV03-01

Translation of the original operating instructions

3. TECHNICAL DATA

3.1 Product drawing

All dimensions in mm.

1

Inlet ring with pressure tap (k-factor: 1200)

2

Mounting position for vibration-absorbing elements, tightening torque max. 40 Nm

3

Cable diameter min. 5 mm, max. 13 mm, tightening torque 4 ± 0.6 Nm

4

Cable diameter min. 16 mm, max. 20.5 mm, tightening torque 6 ± 0.9 Nm

5

Tightening torque 3.5 ± 0.5 Nm

6

Mounting holes for FlowGrid

7

Installation position: shaft horizontal (motor support plate must stand upright) or rotor on bottom; rotor on top on request

Item no. 55793-5-9970 · ENU · Change 94781 · Approved 2018-01-23 · Page 4 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3GA00-PV03-01

Страница 1: ...e permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devi...

Страница 2: ...come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and cause injuries Take appropriate safety measures WARNING Rotatin...

Страница 3: ...mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter 3 6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protectiv...

Страница 4: ...max 13 mm tightening torque 4 0 6 Nm 4 Cable diameter min 16 mm max 20 5 mm tightening torque 6 0 9 Nm 5 Tightening torque 3 5 0 5 Nm 6 Mounting holes for FlowGrid 7 Installation position shaft horiz...

Страница 5: ...n in a standardized measurement setup 3 4 Technical description Weight 178 4 kg Size 1000 mm Motor size 200 Rotor surface Painted black Electronics housing material Die cast aluminum Impeller material...

Страница 6: ...d in the support structure that can be used for transport After installation ensure that the blades on the fan impeller are not deformed or bent CAUTION Risk of cutting and crushing when removing devi...

Страница 7: ...ater ingress at the customer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be switched off with a...

Страница 8: ...LA 4 3 Connection in terminal box 4 3 1 Preparing cables for connection Only strip the cable as far as necessary ensuring that the cable gland is sealed and there is no strain on the connections For t...

Страница 9: ...M control Mode parameter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes Set value requirement Analog linear Direction of action parameter set 1 Positive hea...

Страница 10: ...tact changeover contact common connection contact rating 250 VAC max 2 A AC1 min 10 mA KL2 3 NC Status relay floating status contact break for failure KL 3 1 RSA Bus connection RS485 RSA MODBUS RTU SE...

Страница 11: ...EPROM setting the integrated controller s direction of action can be selected via bus or digital input Din3 normal pin open or applied voltage 5 50 VDC inverse bridge to GND or applied voltage 1 VDC S...

Страница 12: ...ssively high vibration levels and possibly resonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or...

Страница 13: ...matically Device restarts automatically without warning Faulty connection Isolate from supply correct connection see connection diagram Broken motor winding Replace device Deficient cooling Improve co...

Страница 14: ...ce device 6 4 Disposal For ebm papst environmental protection and resource preservation are top priority corporate goals ebm papst operates an environmental management system which is certified in acc...

Страница 15: ...aterials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power cables Cables for internal wiring Electrolyti...

Отзывы: