ebm-papst K3G400-AQ23-01 Скачать руководство пользователя страница 7

Operating instructions

K3G400-AQ23-01

Tr

anslation of the or

iginal oper

ating instr

uctions

3.7 Electromagnetic compatibility

EMC interference

immunity

Acc. to EN 61000-6-2 (industrial

environment)

EMC interference

emission

Acc. to EN 61000-6-3 (household

environment)

If several devices are switched in parallel on the mains side so

that the line current of the arrangement is in the range of 16 - 75

A, then this arrangement conforms to IEC 61000-3-12 provided

that the short-circuit power S

sc

at the connection point of the

customer system to the public power system is greater than or

equal to 120 times the rated output of the arrangement.

It is the responsibility of the installation engineer or operator/

owner of the device to ensure, if necessary after consultation

with the network operator, that this device is only connected to

a connection point with a S

sc

value that is greater than or equal

to 120 times the rated output of the arrangement.

4. CONNECTION AND START-UP

4.1 Connecting the mechanical system

CAUTION

Cutting and crushing hazard when removing the fan

from the packaging

→ Carefully remove the fan from its packaging. Make sure to

avoid any shock.

→ Wear safety shoes and cut-resistant safety gloves.

CAUTION

Heavy load when taking out the device

Bodily harm, e.g. back injuries, are possible.
→ Two people should remove the device out of its packaging

together.

;

Check the device for transport damage. Damaged devices must no

longer be installed.

;

Install the undamaged device according to your application.

4.2 Connecting the electrical system

DANGER

Electric voltage on the device

Electric shock
→ Always install a protective earth first.
→ Check the protective earth.

DANGER

Incorrect insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

requirements for voltage, current, insulation material, load etc.

→ Route cables such that they cannot be touched by any

rotating parts.

DANGER

Electrical load (>50 µC) between mains wire and

protective earth connection after switching of the supply

when switching multiple devices in parallel.

Electric shock, risk of injury
→ Make sure that sufficient protection against accidental contact

is provided.

Before working on the electrical connection, the

connections to the mains supply and PE must be shorted.

CAUTION

Electrical voltage

The fan is a built-in component and features no electrically

isolating switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole separating switch.

→ When working on the fan, you must switch off the

installation/machine in which the fan is installed and secure it

from being switched on again.

NOTE

Interferences and failures are possible

Maintain a distance to the power supply line when routing the

control lines of the device.
→ Ensure a sufficiently large clearance.

Recommendation: clearance > 10 cm (separate cable

routing)

Item no. 50647-5-9970 · ENG · Revision 82549 · Release 2014-05-08 · Page 6 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G400-AQ23-01

Страница 1: ......

Страница 2: ...to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is...

Страница 3: ...on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bo...

Страница 4: ...ce in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustain...

Страница 5: ...ameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm 4 Mounting position shaft horizontal install the support struts only vertically as shown in the view or rotor on bot...

Страница 6: ...fer to product drawing Condensate discharge holes Rotor side Operation mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V Inp...

Страница 7: ...er be installed Install the undamaged device according to your application 4 2 Connecting the electrical system DANGER Electric voltage on the device Electric shock Always install a protective earth f...

Страница 8: ...AC 16 A 15 A C16A 1 5 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 3 PE AC 380 480 VAC 32 A 30 A C32A 6 0 10 AWG American Wire Gauge 4 2 3 Idle current Becaus...

Страница 9: ...e corresponding terminals Use a screwdriver to do so During the connection work ensure that no cables splice off Fig 2 Connecting the wires to terminals Seal the terminal box 4 3 3 Cable routing No wa...

Страница 10: ...n pin or applied voltage 5 50 VDC disabling bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 parameter set s...

Страница 11: ...fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the devi...

Страница 12: ...Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up...

Страница 13: ...nst accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual...

Отзывы: