background image

Operating instructions

K3G400-AK11-H8

Translation of the original operating instructions

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on your device. Send the device to ebm-
papst for repair or replacement.

WARNING
Live terminals and connections even with device
switched off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
If control voltage or a stored speed set value is applied,
the motor will restart automatically, e.g. after a power
failure.

Risk of injury
→ Keep out of the device’s danger zone.
→ When working on the device, switch off the line voltage

and ensure that it cannot be switched back on.

→ Wait until the device comes to a stop.
→ After working on the device, remove any tools or other

objects from the device.

NOTE

If the device is not operated for a lengthy period in installed
condition in a dry environment, it is to be started up and
operated at full speed for one hour at least every four months. If
the device is not operated for a lengthy period in installed
condition in a damp environment (e.g. outdoors), it is to be
started up and operated at full speed for at least two hours once
a month to move the bearings and allow any condensate that
may have ingressed to evaporate.

Malfunction/fault

Possible cause

Possible remedy

Impeller not
running smoothly

Imbalance in rotating
parts

Clean the device;
replace it if imbalance
persists after cleaning.
Make sure no
weight clips are
removed during
cleaning.

Motor not turning

Mechanical blockage

Switch off, isolate
from supply and
remove mechanical
blockage.

Line voltage faulty

Check line voltage,
restore power
supply, apply control
signal.

Faulty connection

Isolate from supply,
correct connection;
see connection
diagram.

Motor/electronics
overtemperature

Deficient cooling

Improve cooling. Let
the device cool down.
To reset the error
message, switch off
the line voltage for at
least 25 s and then
switch it on again.

Thermal overload
protector activated

Allow motor to cool
off, locate and rectify
cause of error,
release restart lockout
if necessary

Ambient temperature
too high

Reduce the ambient
temperature.
Reset by reducing
control input to 0.

Impermissible point of
operation

Correct the operating
point. Let the device
cool down.

In the event of further malfunctions, contact ebm-papst.

6.1 Vibration testing

Checking of fan for mechanical vibration based on ISO 14694.
Recommendation: Every 6 months. Max. vibration severity is 3.5 mm/
s, measured at the motor fastening diameter on the motor support plate in
the direction of the motor axis of rotation and perpendicular to this.

Fig. 1: Example illustrating vibration measurement. The arrangement of
the sensors depends on the device concerned and the installation
situation.

6.2 Cleaning

To ensure a long service life, check the fans regularly for proper
operation and soiling. The frequency of checking is to be adapted
accordingly depending on the degree of soiling.

DANGER
Risk of injury from rotating fan.

→ Only clean when not in motion. Do not disconnect the fan

from the power supply, just switch it off via the control input.
This will prevent start-up of the fan.

;

Dirt deposits on the motor housing can cause overheating of the motor.

;

Soiling of the impeller can cause vibration that will shorten the service
life of the fan.

;

Severe vibration can destroy the fan.

;

In such cases, switch off the fan immediately and clean it.

;

The preferred method of cleaning is dry cleaning, e.g. using
compressed air.

;

Do not use aggressive cleaning agents!

;

Completely remove any cleaning agents used.

Item no. 54222-5-9970 · ENU · Change 211930 · Approved 2020-01-29 · Page 11 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание K3G400-AK11-H8

Страница 1: ...d specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associat...

Страница 2: ...g on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the...

Страница 3: ...ve devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e...

Страница 4: ...2 Connector housing 3 pole GST18 3 Wieland 92 032 9058 1 2 1 N 2 2 PE 2 3 L 3 8 pole socket housing tyco 100616 2 4 8 pole socket housing tyco 100616 2 Item no 54222 5 9970 ENU Change 211930 Approved...

Страница 5: ...evel The ErP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 8 9 kg Size 400 mm Motor size 84 Rotor surface Painted black Ele...

Страница 6: ...move the device from the packaging by grasping hold of the frame Never subject to any impact Wear safety shoes and cut resistant safety gloves NOTE Damage to the device from vibration Bearing damage s...

Страница 7: ...r integrated for compliance with EMC limits interference emission and immunity to interference reactive currents can be measured in the supply line even when the motor is at a standstill and the line...

Страница 8: ...RS485 RSA MODBUS RTU SELV 2 2 RSB Bus connection RS485 RSB MODBUS RTU SELV 2 3 GND Reference ground for control interface SELV 2 4 0 10 V Control input 2 5 10 V Fixed voltage output 10 VDC 2 6 RES Res...

Страница 9: ...interface SELV 3 4 0 10 V Control input 3 5 10 V Fixed voltage output 10 VDC 3 6 RES Reserve 3 7 COM Alarm COM 3 8 NC NC KL3 UMAX 24 V 3 9 Schirm Shield Item no 54222 5 9970 ENU Change 211930 Approved...

Страница 10: ...e with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum permissible vibration severity must not exceed 3 5 mm s and shoul...

Страница 11: ...overtemperature Deficient cooling Improve cooling Let the device cool down To reset the error message switch off the line voltage for at least 25 s and then switch it on again Thermal overload protect...

Страница 12: ...em which is certified in accordance with ISO 14001 and rigorously implemented around the world on the basis of German standards Right from the development stage ecological design technical safety and...

Страница 13: ...ploying the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 54222 5 9970 ENU Change 211930 Approved 2020 01 29 Page 13 13 ebm papst Mulfinge...

Отзывы: