4.2.1 Requirements

;

Check whether the information on the nameplate matches the
connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

4.2.2 Reactive currents

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and immunity to interference),
reactive currents can be measured in the supply line even
when the motor is at a standstill and the line voltage is switched
on.

The values are typically in the range < 250 mA

At the same time, the effective power in this operating state
(operational readiness) is typically < 4 W.

4.2.3 Residual current circuit breaker (RCCB)

Only universal residual current devices (type B or B+) are
allowed. As with variable frequency drives, residual current
devices cannot provide personal safety while operating the
device.
When the device's power supply is switched on, pulsed
charging currents from the capacitors in the integrated EMC
filter can lead to the residual current devices tripping without
delay. We recommend the use of residual current circuit
breakers with a trip threshold of 300 mA and delayed tripping
(super-resistant, characteristic K).

4.2.4 Locked-rotor protection

Due to the locked-rotor protection, the starting current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Plug connection

4.3.1 Making supply connections

CAUTION
Voltage

The device is a built-in component and has no disconnecting
switch.
→ Connect the device to a suitable tripping unit.
→ Only connect the device to circuits that can be switched

off with an all-pole disconnection switch.

→ When working on the device, secure the system/

machine in which the device is installed so as to prevent it
from being switched back on.

;

Check your connector's pin assignment.

;

Connect the built-in connector with the mating connector.

;

Ensure that the connector is properly engaged.

Item no. 50131-5-9970 · ENU · Change 72552 · Approved 2012-08-17 · Page 7 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание G3G200-GN18-01

Страница 1: ...qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic s...

Страница 2: ...is EMC compliant 1 7 Mechanical movement DANGER Danger of injury from open blower Escaping gas When the blower is open you come into contact with rotating and electrically live parts Escaping gas can...

Страница 3: ...storage conditions and Chapter 3 2 Nominal data Using the device only in stationary systems Installing the device in an integrated system for conveying air Commissioning the built in component only a...

Страница 4: ...6 1 socket tyco no 926884 1 1 1 L 1 2 N 1 3 PE 2 5 pole header fits mating connector not included in scope of delivery Molex no 39 01 4050 socket Molex no 39 00 0059 2 1 2 2 Speed monitoring 2 3 0 10...

Страница 5: ...rent from the measurement category are detailed in the CE declaration Specific ratio 1 pfs 100 000 Pa Data obtained at optimum efficiency level The ErP data is determined using a motor impeller combin...

Страница 6: ...should be isolated from vibration e g using compensators or similar elements Ensure stress free attachment of the fan to the substructure Check the device for transport damage Damaged devices are not...

Страница 7: ...wed As with variable frequency drives residual current devices cannot provide personal safety while operating the device When the device s power supply is switched on pulsed charging currents from the...

Страница 8: ...B external voltage 16 45 VDC maximum ripple 3 5 SELV ST2 2 Tach Speed monitoring 3 pulses per revolution SELV ST2 3 0 10 V Control input 0 10 V impedance 100k SELV ST2 4 PWM Control input PWM 1 6 kHz...

Страница 9: ...via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connec...

Страница 10: ...tion At least every 6 months Replace cables Condensation drainage holes for clogging where necessary Visual inspection At least every 6 months Open holes Abnormal bearing noise acoustic At least every...

Страница 11: ...wires are made of similar materials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power cables Cables for...

Отзывы: