Operating instructions

D2E146-HT67-60

Translation of the original operating instructions

4.6 Checking the connections

;

Make sure that the power is off (all phases).

;

Secure it from being switched on again.

;

Check that the mating connector is correctly locked into the panel
connector.

;

Check that the mating connector is correctly crimped to the
connection line.

4.7 Switch on device

WARNING
Hot motor housing

Fire hazard
→ Ensure that no combustible or flammable materials are

located close to the blower.

;

Inspect the device for visible external damage and the proper function
of the protective features before switching it on.

;

Check the air flow paths of the fan for foreign objects and remove any
that are found.

;

Apply the nominal voltage to the voltage supply.

4.8 Switching off the device

;

Disconnect the device from the supply voltage at the main switch for
the supply line.

;

When disconnecting, be sure to disconnect the earth wire connection
last.

5. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on your device. Return the device to ebm-
papst for repair or replacement.

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
Electrical load on the capacitor after device is switched off

Electric shock, risk of injury
→ Discharge the capacitors before working on the device.

CAUTION
The motor restarts automatically when operating voltage
is applied, e.g. after a power failure.

Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains

supply voltage and secure the latter from being switched on
again.

→ Wait until the device stops.

If the device remains out of use for some time, e.g. when in
storage, we recommend switching the device on for at least
two hours to allow any condensate to evaporate and to move
the bearings.

Malfunction/error

Possible cause

Possible remedy

Impeller running
roughly

Imbalance in rotating
parts

Clean the device; if
imbalance is still
evident after
cleaning, replace the
device.
If you have
attached any weight
clips during cleaning,
make sure to
remove them
afterwards.

Motor does not turn

Mechanical blockage

Switch off, de-
energise, and
remove mechanical
blockage.

Mains supply
voltage faulty

Check mains supply
voltage,
restore power
supply.

Faulty connection

De-energise, correct
connection, see
connection diagram.

Thermal overload
protector responded

Allow motor to cool
off, locate and rectify
cause of error, if
necessary cancel
restart lock-out

Item no. 11187-5-9970 · Revision 72138 · Release 2010-11-02 · Page 8 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание D2E146-HT67-60

Страница 1: ...ed and authorised specialist personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions ...

Страница 2: ... could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emission WARNING Depending on the installation and operating conditions a sound pressure level greater than 70 dB A may arise Danger of noise induced hearing loss Take appropriate technical safety measures Protect...

Страница 3: ... the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and protected accordingly Moving air that contains dust pollution e g suctioning off saw dust Operatin...

Страница 4: ...tage 2 1 3 L stage 3 1 4 L stage 4 1 5 N 1 6 Protective earth 2 Connector shell Molex 39 01 2040 6x female connector Molex 39 00 0065 2 1 red 2 2 black 2 3 white 3 4 x sheet metal nut for thread EN ISO 1478 ST4 8 min screw length 14 5 mm plus thickness of mounting material Item no 11187 5 9970 Revision 72138 Release 2010 11 02 Page 4 9 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen P...

Страница 5: ...kwise seen on rotor Type of protection IP 20 Insulation class F Humidity class F0 Mounting position Any Condensate discharge holes None open rotor Operation mode S1 Motor bearing Ball bearing Speed steps 4 Touch current acc IEC 60990 measuring network Fig 4 TN system 0 75 mA Electrical leads With plug Motor protection Thermal overload protector TOP wired internally Cable exit Variable Protection c...

Страница 6: ...witched off using an all pole disconnecting switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data and the data of the operating capacitor Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for current according to the type plate For determining the cross section follow the bas...

Страница 7: ...ds switch must break the circuit 1 Step 1 min 2 Step 2 3 Step 3 4 Step 4 max 5 N 6 TOP 2x 7 Protective earth 8 Speed increase Item no 11187 5 9970 Revision 72138 Release 2010 11 02 Page 7 9 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 8: ...ectrical load on the capacitor after device is switched off Electric shock risk of injury Discharge the capacitors before working on the device CAUTION The motor restarts automatically when operating voltage is applied e g after a power failure Danger of injury Keep out of the danger zone of the device When working on the device switch off the mains supply voltage and secure the latter from being ...

Страница 9: ...Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Mounting of protective earth connection Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage Visual inspection At least every ...

Отзывы: