background image

Operating instructions

D2E146-HT67-60

Translation of the original operating instructions

3.2 Nominal data

Motor

M2E068-EC

Phase

1~

1~

Nominal voltage / VAC

230

230

Frequency / Hz

50

60

Type of data definition

ml

ml

Valid for approval /
standard

CE

CE

Speed / min

-1

2200

2150

Power input / W

305

395

Current draw / A

1.34

1.73

Motor capacitor / µF

8

8

Capacitor voltage / VDB

450

450

Capacitor standard

P2 (CE)

P2 (CE)

Min. back pressure / Pa

250

235

Max. ambient
temperature / °C

55

55

Starting current / A

1.8

ml = max. load · me = max. efficiency · fa = running at free air

cs = customer specs · cu = customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

No

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

29

27

34

Efficiency grade N

39

37

44

Power input P

e

/ kW

0.26

Air flow q

v

/ m³/h

700

Pressure increase total p

sf

/ Pa

400

Speed n / min

-1

2435

Data established at point of optimum efficiency

3.4 Technical features

Mass

3.7 kg

Size

146 mm

Material of terminal box

PP plastic, black

Material of impeller

Sheet steel, hot-galvanised

Housing material

PP plastic, black

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 20

Insulation class

"F"

Humidity class

F0

Mounting position

Any

Condensate discharge
holes

None, open rotor

Operation mode

S1

Motor bearing

Ball bearing

Speed steps

4

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

< 0.75 mA

Electrical leads

With plug

Motor protection

Thermal overload protector (TOP) wired
internally

Cable exit

Variable

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 60335-2-31; CE

Approval

CCC; CSA C22.2 Nr.113; UL 507

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

For depth of screw, see chapter 3.1 Product drawing

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

Item no. 11187-5-9970 · Revision 72138 · Release 2010-11-02 · Page 5 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание D2E146-HT67-60

Страница 1: ...ed and authorised specialist personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions ...

Страница 2: ... could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emission WARNING Depending on the installation and operating conditions a sound pressure level greater than 70 dB A may arise Danger of noise induced hearing loss Take appropriate technical safety measures Protect...

Страница 3: ... the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mist Exceptions are devices that are intended for salt spray mist and protected accordingly Moving air that contains dust pollution e g suctioning off saw dust Operatin...

Страница 4: ...tage 2 1 3 L stage 3 1 4 L stage 4 1 5 N 1 6 Protective earth 2 Connector shell Molex 39 01 2040 6x female connector Molex 39 00 0065 2 1 red 2 2 black 2 3 white 3 4 x sheet metal nut for thread EN ISO 1478 ST4 8 min screw length 14 5 mm plus thickness of mounting material Item no 11187 5 9970 Revision 72138 Release 2010 11 02 Page 4 9 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen P...

Страница 5: ...kwise seen on rotor Type of protection IP 20 Insulation class F Humidity class F0 Mounting position Any Condensate discharge holes None open rotor Operation mode S1 Motor bearing Ball bearing Speed steps 4 Touch current acc IEC 60990 measuring network Fig 4 TN system 0 75 mA Electrical leads With plug Motor protection Thermal overload protector TOP wired internally Cable exit Variable Protection c...

Страница 6: ...witched off using an all pole disconnecting switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data and the data of the operating capacitor Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for current according to the type plate For determining the cross section follow the bas...

Страница 7: ...ds switch must break the circuit 1 Step 1 min 2 Step 2 3 Step 3 4 Step 4 max 5 N 6 TOP 2x 7 Protective earth 8 Speed increase Item no 11187 5 9970 Revision 72138 Release 2010 11 02 Page 7 9 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 8: ...ectrical load on the capacitor after device is switched off Electric shock risk of injury Discharge the capacitors before working on the device CAUTION The motor restarts automatically when operating voltage is applied e g after a power failure Danger of injury Keep out of the danger zone of the device When working on the device switch off the mains supply voltage and secure the latter from being ...

Страница 9: ...Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Mounting of protective earth connection Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage Visual inspection At least every ...

Отзывы: