         CN1090                                 

 

Installation 

 

General: 

See “Safety” information above. 
For connections, see Connection Details table above. Route control wiring separately from AC mains wiring. 
Remove enclosure knock-outs as required to fit cable glands, taking care not to damage the PCB. Cable entry at 
enclosure end is recommended. 

Tools: 

A 2.5mm flat screwdriver is recommended for the screw terminal block clamps and Variable Resistor adjustment. 
A voltmeter is required during commissioning. 

230VAC Supply: 

Controller connection to 230VAC supply must be fused to 13A maximum. 
The supply for single phase fans up to 13A total load may be connected via this control PCB, connect Fans to 
230VAC output and Earth output terminals. For higher currents or 3-phase fans route supply direct to fans. 

Proportional Band Control: 

Connect first sensor to “0-10V Input, Sensor One“ (J3 pin 3) and “0V“ (J3 pin 6), plus “24VDC Unregulated 
Output, 25mA max“ (J3 pin 9) if required  
If used, connect second sensor or Local / Remote BMS 0-10V control to “0-10V Input, Sensor Two / External 
Pressure Set-point 0-10V input“ (J3 pin 5) and “0V“ (J3 pin 8), plus “24VDC Unregulated Output, 25mA max“ (J3 
pin 9) if required. 

Constant Pressure Control: 

Connect pressure sensor to “0-10V Input, Sensor One“(J3 pin 3) and “0V“ (J3 pin 6), plus “24VDC Unregulated 
Output, 25mA max“(J3 pin 9) if required. 
If used, connect External Pressure Set-point 0-10V to “0-10V Input, Sensor Two / External Pressure Set-point 0-
10V input“(J3 pin 5) and “0V“(J3 pin 8). 

Fans: 

Connect fan supply, speed control and tachometer leads, see table above for connections. If fan has a 10V 
output wire cut back & insulate. If fans are Alarm Relay type (not Tachometer), connect fan relay between 0V and 
tachometer Input. If fan monitoring is not required, then link tachometer Input to 0V to prevent alarms. 

Select Inputs: 

Connect Run/Stop and Speed/Set-point select inputs as required for the application, see Tables below. 

PCB Switches and Variable Resistors: 

Set DIP Switches and Variable Resistors as required, see tables and procedures below. 
 

DIP Switch 1 

Position 

OFF 

ON 

Proportional Band Control mode

 

Constant Pressure PID Control mode

 

Two Fans

 

Single Fan, Fan1 only

 

3,4 

Simultaneous / Alternate Fan Run Changeover Period Run, see table 

5, 6 

See tables below 

Fan 1 PWM, Open Collector 

Fan 1 PWM, 0-10V 

Fan 2 PWM, Open Collector 

Fan 2 PWM, 0-10V 

 

DIP Switch 1 

Position

 

Simultaneous / Alternate Fan Run 

Changeover Period (Hours) 

 

Fan Fail action 

Off 

Off 

Simultaneous Fan Run (Alternate run at low airflow) 

Remaining fan runs faster 

ON 

Off 

 

Swap to standby fan  

Off 

ON 

12 

ON 

ON 

24 

 

See 

Proportional Control Band 

or 

Constant Pressure Control 

sections below for additional settings.

 

Содержание CN1090

Страница 1: ...re Control Commissioning 9 Controller Operation General Run Enable Inputs LED s Relays Power up Check 12 Fan Run Control 12 Fan Monitor 12 Alarm Relay 12 Fan Run Relay 12 Fan Maximum Speed Relay Change over contacts 12 Power up Check 12 Maintenance and Servicing 12 Use of ebm papst RM ECv Controller for local manual control 12 Terminal Block Use 13 PCB Component Location and Live SELV Circuit 14 D...

Страница 2: ... Supply Current A 0 05 Amps plus Fan load if wired via PCB 13A max Alarm Relays Contact rating 100mA max 60VDC max 0 10V Inputs 100kOhm impedance minimum PWM frequency 2kHz Operating Environment 30 to 60C IP66 Enclosure Connection Details see Terminal Block Use below Mains Connector J1 Pin Function SL1 1 Switched Live 1 Fan Speed Set point select input SL2 2 Switched Live 2 Stop Run control input ...

Страница 3: ...an2 Run and Alarm indicated by PCB silk screen legend LED En Run Enable and LED B Fast indicated by PCB silk screen legend Trimmer Identification Trimmer indicated by PCB silk screen legend R1 R2 R3 and R4 IP Rating IP66 with Enclosure Cable Glands Not included Enclosure supplied has knock outs to suit 16mm or 20mm glands Safety Installation must be by qualified personnel in accordance with local ...

Страница 4: ...gulated Output 25mA max J3 pin 9 if required Constant Pressure Control Connect pressure sensor to 0 10V Input Sensor One J3 pin 3 and 0V J3 pin 6 plus 24VDC Unregulated Output 25mA max J3 pin 9 if required If used connect External Pressure Set point 0 10V to 0 10V Input Sensor Two External Pressure Set point 0 10V input J3 pin 5 and 0V J3 pin 8 Fans Connect fan supply speed control and tachometer ...

Страница 5: ...an speed demand levels Select inputs can be used to force the Fan Speed to Minimum Maximum or set to the Proportional Band Demand Speed The Variable Resistors and rotary DIP switches configure the operation as shown below Example Proportional Band Control Profile Sensor 1 0 1 2 3 4 5 6 7 8 9 10V Example Proportional Band Control Profile Sensor 2 0 1 2 3 4 5 6 7 8 9 10V Max speed Rotary Switch S3 S...

Страница 6: ...missioning see table below 6 SL1 selects Sensor Demand Fan Speed SL1 selects Maximum Fan Speed S3 setting DIP Switch 1 Position Proportional Band Control Commissioning 5 6 PWM Outputs Indicator LED ON Off Fan 1 Speed Control PWM Output R1 Setting Fan 2 Speed Control PWM Output R2 Setting NTC1 Red LED Pulse ON ON Fan 1 Speed Control PWM Output R3 Setting Fan 2 Speed Control PWM Output R4 Setting NT...

Страница 7: ...connect Sensor 2 set points to the controller Fan Speed outputs NTC2 Red LED pulses 11 Connect a Voltmeter to Fan 1 Speed Control PWM Output J2 pin 3 12 Adjust R3 for a voltmeter reading equal to the Sensor 2 Bottom of proportional control band voltage 13 Move the Voltmeter to Fan 2 Speed Control PWM Output J2 pin 6 14 Adjust R4 for a voltmeter reading equal to the Sensor 2 Top of proportional con...

Страница 8: ...ntrol Fan Minimum and Maximum speeds Adjust Rotary DIP Switch S2 to set the fan Minimum speed control voltage Adjust Rotary DIP Switch S3 to set the fan Maximum speed control voltage See table below Rotary DIP Switch Position Fan Speed Voltage 0 0 1 2 0 2 2 6 3 3 1 4 3 7 5 4 2 6 4 8 7 5 3 8 5 9 9 6 4 A 7 0 B 7 5 C 8 1 D 8 6 E 9 2 F 10 0 To invert Speed Control Output Heating Profile make S2 settin...

Страница 9: ...ect input use Refer to the datasheet for the pressure sensor used to determine the sensor output voltage at the required pressure set point then adjust rotary switch S3 to select the value closest to the required point see table below BMS External Potentiometer Set point if used See table for select input use If selected the Set point voltage will be the voltage present on 0 10V Input 2 min max no...

Страница 10: ...0V Linked to 0V SL1 Switched Live Input 1 J1 pin 1 Open Linked to 230VAC and DIP SW 6 OFF Linked to 230VAC and DIP SW 6 ON Volt Free Select Input 1 J2 pin 9 Open Linked to 0V Volt Free Select Input 2 J2 pin 13 Open Open Open Linked to 0V In the above table indicates Input state ignored DIP Switch 1 Position Constant Pressure Control operation OFF ON 5 Normal Cooling Profile Invert Speed Control Ou...

Страница 11: ...6 e mail sales uk ebmpapst com CN1090 Constant Pressure Control Low and High Set points Adjust Rotary DIP Switch S2 to set the Low Single Pressure Set point voltage Adjust Rotary DIP Switch S3 to set the High Second Pressure Set point voltage See table below Rotary DIP Switch S2 S3 Position Pressure Set point Voltage 0 0 6 1 1 2 2 1 9 3 2 5 4 3 1 5 3 7 6 4 3 7 5 0 8 5 6 9 6 2 A 6 8 B 7 4 C 8 1 D 8...

Страница 12: ...y Energised fan below maximum speed setting Relay De energised fan at maximum speed setting may indicate Filter Block on a filtered system Power up Check At power up all LED s will illuminate and Relays energise for a few seconds The fan run will be checked unless Fan Stop is selected Maintenance and Servicing The PCB has no replaceable parts if a fault develops return the PCB to the manufacturer ...

Страница 13: ...ed as follows Insert a 2 5mm or 3mm flat blade screwdriver fully into the upper hole as shown to open the terminal wire entry Insert the wire into the lower hole then remove the screwdriver to leave the wire clamped in the terminal Alternatively open the wire entry by inserting the screwdriver fully from the opposite side of the connector as shown Insert the wire into the lower hole then remove th...

Страница 14: ...mail sales uk ebmpapst com CN1090 PCB Component Location and Live SELV Circuit Key PCB components are shown below J1 Pin1 High Speed Run Enabled S1 S2 S3 LED B LED En Live Circuit SELV Circuit R1 R2 R3 R4 NTC1 NTC2 LED LED R1 R2 R3 R4 Proportional Band TEST TEST TEST TEST Commissioning POINT POINT POINT POINT Fan1 Run Fan2 Run J3 Pin1 LED LED Fan1 Alarm Fan2 Alarm J2 Pin1 LED LED Rotary DIP Switch...

Страница 15: ...3277_Iss1 doc ORIGINAL INSTRUCTIONS Page 15 of 15 ebm papst UK Ltd 2012 Chelmsford Business Park Chelmsford Essex CM2 5EZ Telephone 44 0 1245468555 Fax 44 0 1245466336 e mail sales uk ebmpapst com CN1090 Declaration of Conformity 13 02 2013 15 08 58 ...

Отзывы: