Operating and Maintenance Instructions
210-OMI13277_Iss1.doc
ORIGINAL INSTRUCTIONS
Page 10 of 15
© ebm-papst UK Ltd, 2012
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail
CN1090
Pressure Set-point
Select Inputs
FAN STOP
Constant Pressure Set-point
Low / Single
Pressure
Set-point
(S2)
External Pressure
Set-point
(0-10V Input 2)
High Pressure
Set-point
(S3)
SL2, Switched
Live Input 2
Stop/Run
(J1 pin 2)
Open
-
Linked to
230VAC
Linked to
230VAC
Linked to
230VAC
Volt Free Stop/Run
(J1 pin 11)
-
Open
Linked to 0V
Linked to 0V
Linked to 0V
SL1, Switched
Live Input 1
(J1 pin 1)
-
-
Open
-
Linked to
230VAC,
and
DIP SW 6
OFF
-
Linked to
230VAC,
and
DIP SW 6
ON
Volt Free Select
Input 1
(J2 pin 9)
-
-
Open
Linked
to 0V
-
-
-
Volt Free Select
Input 2
(J2 pin 13)
-
-
Open
Open
Open
Linked
to 0V
-
In the above table “-” indicates “Input state ignored”
DIP Switch 1
Position
Constant Pressure Control operation
OFF
ON
5
Normal (Cooling Profile)
Invert Speed Control Output (Heating Profile)
6
SL1 selects 0-10V set-point
SL1 selects Rotary Switch S3 set-point
Constant Pressure Control Set-points
Rotary DIP Switch
S2
Low Pressure Set-point
0-10V Input 2 (J3 pin 5)
External Pressure Set-point
Rotary DIP Switch
S3
High Pressure Set-point
Variable
Resistor
Constant Pressure Control
R1
PID Gain (response speed)
R2
Fan Maximum Speed
R3
(reserved)
R4
(reserved)