Operating and Maintenance Instructions
210-OMI13277_Iss1.doc
ORIGINAL INSTRUCTIONS
Page 11 of 15
© ebm-papst UK Ltd, 2012
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail
CN1090
Constant Pressure Control, Low and High Set-points:
Adjust Rotary DIP Switch S2 to set the Low / Single Pressure Set-point voltage.
Adjust Rotary DIP Switch S3 to set the High / Second Pressure Set-point voltage.
See table below
Rotary DIP Switch S2 & S3
Position
Pressure Set-point
Voltage
0
0.6
1
1.2
2
1.9
3
2.5
4
3.1
5
3.7
6
4.3
7
5.0
8
5.6
9
6.2
A
6.8
B
7.4
C
8.1
D
8.7
E
9.3
F
10.0