Precautions of safety     

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Warning 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On handling and installation work of the pump, assure safety by confirming the mass and 

the  shape  of  the  pump  referring  to  the  appearance  this instruction  manual,  drawing,  the 

catalogue, and other materials. There are dangers of dropping the pump and the injury of 

worker. 

 

Never  execute  the  operation  of  the  pump  and  the  mounting  work  of  parts  in  a  lifted 

position.  That  type  of  work  is  dangerous  causing  dropping  of  the  pump  and  injury  of 

worker. 

 

Do  not  damage,  break,  machine,  forcefully  bend,  stretch,  or  twist  the  power  cable,  bind 

the power cable into a bundle, or place a heavy load on the power cable. Those kinds of 

handling cause fire and electric shock. 

 

Execute correct wiring work by a qualified technician conforming to the  appropriate legal 

standards. Wrong wiring by non-qualified worker is illegal and may induce electric shock 

and fire. 

 

Do  apply  grounding  wiring.  The  Green  and  Yellow  stripe  cord  or  the  Green  cord  is  the 

grounding  line.  Never  connect  the  Green  and  Yellow  stripe  cord  to  the  power  source 

because there is a possibility of electric shock in case of trouble or electric leak. 

 

To prevent electric shock, install an exclusive use ground fault breaker. The electric leak 

may cause electric shock and fire. 

 

If any dust is attached to a blade or blade-attaching face of the power source plug, fully 

wipe the dust off with a dry-cloth. The attached dust may cause fire. 

 

During  operation  of  the  pump,  do  not  insert  hand  or  foot  in  the  suction  opening  of  the 

pump to avoid injury at the rotary section. 

 

Never operate the pump in water in the presence of personnel. 

If electric leak occurs, the personnel may suffer electric shock. 

 

Disassembling, repairing, and modifying the pump shall be limited to a repair technician. 

There  is  a  possibility  of  injury  caused  by  electric  shock,  ignition,  abnormal  functioning, 

trouble, etc. 

 

Before  entering  inspection  and  repair,  cut  OFF  a  power  source  at  a  main  disconnect 

device  which  is  equipped  with  an  operating  handle  which  is  lockable  in  OFF  position.   

There is a possibility of electric shock and of injury caused by sudden start of the pump in 

automatic operation mode. 

 

To stop operation for a certain period, cut OFF the power switch. 

Deterioration of insulation may cause electric shock, electric leak, and fire. 

 

The user of a standard model shall refer to the columns of standard specification. Do not 

use  the  pump  at  outside  the  range  of  the  specification  in  terms  of  handling  liquid, 

installing site, power source, etc. Operation at outside the specification may cause pump 

trouble, injury, electric shock, electric leak, and fire. 

 

Do  not  execute  dry  operation  in  air.  That  type  of  operation  causes  deterioration  in 

insulation to lead to electric shock and electric leak. 

 

If  the  insulation  resistance  decreases  to  1MΩ  or  less,  immediately  cut  OFF  the  power 

switch,  and  request  the  inspection  and  repair  of  the  pump  to  the  supplier  or  EBARA 

CORP. There is a possibility of motor burn out, electric shock, and fire. 

 

Confirm non-loosening at the wirings of motor, at the primary and secondary terminals of 

control  panel,  and  at  the  connection  and  wiring  terminals  of  the  power  devices  in  the 

control  panel.  Remove  dust  from  these  sections.  Imperfect  connection  of  wiring  caused 

by loosening and attached dust may cause ignition resulting in fire. 

 

Do not attach parts other than EBARA's standard products, and do not modify EBARA's 

products. There is a possibility of electric shock and ignition, or injury caused by abnormal 

functioning, break, etc. Furthermore, there may fail in performing normal functioning. 

 

Содержание DL

Страница 1: ...ion when protective device is activated 15 Installation 8 1 Confirmation before installation 8 Troubleshooting 17 2 Installation 8 Structure 18 3 Electric wiring 10 1 Sectional view 18 Operation 12 10...

Страница 2: ...ontents shall be observed in any case Description of the indication Terms of warning Description Warning Wrong handling expects to raise a danger resulting in death or serious injury of the operator C...

Страница 3: ...sassembling repairing and modifying the pump shall be limited to a repair technician There is a possibility of injury caused by electric shock ignition abnormal functioning trouble etc Before entering...

Страница 4: ...nt or by leakage of enclosed liquid from mechanical seal Do not use the pump at an important facility computer cooling apparatus cooling apparatus for refrigerator etc Since machining oil rubber relea...

Страница 5: ...the nameplate Specifically care shall be paid on the frequency 50 Hz or 60 Hz Caution Do not operate a pump of 50Hz at 60Hz The operation at wrong frequency induces pump break caused by excess pressur...

Страница 6: ...clusion of foreign matter Do not use the pump at facilities for organisms fish farm fish preserve aquarium etc There is a possibility of extinction of organisms caused by leak current or by leakage of...

Страница 7: ...side Ceramics carbon sliding material at motor side NBR rubber material Turbine oil ISO VG 32 Motor 1 2 Model number of poles Thermal class Phase frequency voltage current Built in protective device D...

Страница 8: ...erval depending on the use environment Depending on the use environment there may be generated rust at threaded sections machined sections with rust proof coating rust proofing sections etc 1 On trans...

Страница 9: ...his will not happen 13 Models DLA and DLJ will undergo automatic alternate operation only when they are paired Position the floats for these automatic alternate operation pumps DLJ as shown in Fig 5 T...

Страница 10: ...needs to be provided in the final installation It is recommended to use a circuit breaker as main breaker that is suitable for isolation according to appropriate legal standard EN60947 2 and is equip...

Страница 11: ...el E among the four lines as shown in Fig 7 Never connect the Green and Yellow stripe cord or the Green cord to the power source The grinding shall be surely conducted conforming to the Technology Sta...

Страница 12: ...ition or at near the operable minimum water level the Auto cut in the motor is actuated If the situation is repeated the pump life becomes short Once the Auto cut is actuated the motor does not start...

Страница 13: ...the pumps are now ready for operation Note Operate the pump at a discharge rate suitable for the facilities Operation at excessively small or large capacity causes noise and vibration and consumes unn...

Страница 14: ...hin the limit of pump rating the pump may have caught foreign matter 2 If the discharge rate showed a sudden decrease foreign matter may have clogged the suction opening 2 Regular inspection 1 Once a...

Страница 15: ...t every disassembly for inspection Every 20000 cycles of operation Every 100000 cycles of operation Expected replacement time One year or 6000 hours of total operating hours either of shorter one Once...

Страница 16: ...and water to a container Then clean the inside the leakage detector s chamber and motor chamber and replace the mechanical seal as well as gaskets and O rings Leakage Detector Contact rating AC280V 0...

Страница 17: ...ace the mechanical seal Liquid quality and operation conditions need to be reviewed Replace the mechanical seal Pumping not effected or insufficient pumping capacity Pump running in reverse rotation G...

Страница 18: ...L SEAL 1 SET 811 SUBMERSIBLE CABLE 1 115 1 O RING 1 814 MOTOR FRAME 1 115 2 O RING 1 816 BRACKET 1 115 3 O RING 1 817 BRACKET 1 117 1 GASKET 1 830 SHAFT 1 117 2 SEAL WATER 1 849 1 BALL BEARING 1 120 1...

Страница 19: ...without contacting with the suction cover Then enter the operation of the pump 11 Limited Warranty EBARA Corporation warrants to the original retail purchaser Customer the followings 1 This warranty v...

Страница 20: ...uires about the pump please contact EBARA Singapore Ebara Engineering Singapore Pte Ltd Website www ebara com sg E mail ebaranet singnet com sg Malaysia Ebara Pumps Malaysia Sdn Bhd Website www ebara...

Отзывы: