3. Test operation

 

  Automatic alternate type pumps (DLJ)  

Check  automatic  alternate  operation  of  pumps  No.  1 

(DLJ) and pump No. 2 (DLA) as follows (See Fig. 9). 

1) When  the  water  level  reaches  pump  No.  1  start  level, 

pump No. 1 will start and water will be pumped until pump 

No.  1  stop  water  level  is  reached.    At  this  point  the 

automatic  alternate  operation  circuit  built  into  pump  No.  1 

will  stop  the  pump.    The  water  level  will  now  be  at  pump 

No.  2  start  level.    Pump  No.  2  will  start  and  pump  water 

until  its  stop  water  level  is  reached.    The  process  is 

repeated when the water level is again at pump No. 1 start 

level. 

2) If the water flowing into the water tank exceeds the amount being pumped by pump No. 2 (abnormal 

water increase) and the water level rises to pump No. 1 abnormal start water level, pump No. 1 will 

start to operate.    The two pumps will then be operating simultaneously in parallel operation. 

* Check the direction of rotation for each pump using  the same measure described in (2) of 2  while 
the pump is operating. 

3) Once  the  direction  of  rotation  is  verified,  gradually  open  the  gate  valves  to  check  for  abnormal 

conditions  in  pressure,  discharge  quantity,  current  value,  etc.,  referring  to 

 

“Troubleshooting.”   

Do not operate the pump with the gate valve fully closed. 

 

4. Operation 

After the test operation is completed, the pumps are now ready for operation.

 

Note

 

Operate the pump at a discharge rate suitable for the facilities. 
(Operation at excessively small or large capacity causes noise and vibration, and 
consumes unnecessary power.) 

 

 

Maintenance 

   

 

 

Warning

 

Disassembling, repairing, and modifying the pump shall be done only by a repair 

technician. 

There  is  a  possibility  of  electric  shock,  ignition,  or  injury  caused  by  abnormal 
functioning, break, etc. 

 

Do  not  attach  parts  other  than  EBARA's  standard  parts,  and  do  not  modify 
EBARA's  standard  products.  Use  of  other  than  the  standard  parts  may  result  in 
electric shock, ignition, or injury caused by abnormal functioning or break, or may 
fail to perform normal functioning. 

 

Before  entering  inspection  and  repair,  cut  OFF  a  power  source  at  a  main 
disconnect device which is equipped with an operating handle which is lockable in 
OFF  position.    There  is  a  possibility  of  electric  shock  and  of  injury  caused  by 
sudden start of the pump in automatic operation mode. 

 

To stop operation for a certain period, cut OFF the power switch. 

Deterioration of insulation may cause electric shock, electric leak, and fire. 

 

If  the  insulation  resistance  decreases  to  1MΩ  or  less,  cut  immediately  OFF  the 
power switch, and request the inspection and repair of the pump to the supplier or 
EBARA CORP. There is a possibility of motor burn-out, electric shock, and fire. 

 

 

 

 

 

 

Pump 
No. 1 
stop water 
level 

Pump No. 2   
stop water level 

Pump No. 1 
abnormal start 
water level 

Pump No. 2 start 
water level 

Pump No. 1 
start water 
level 

Fig.9

Содержание DL

Страница 1: ...ion when protective device is activated 15 Installation 8 1 Confirmation before installation 8 Troubleshooting 17 2 Installation 8 Structure 18 3 Electric wiring 10 1 Sectional view 18 Operation 12 10...

Страница 2: ...ontents shall be observed in any case Description of the indication Terms of warning Description Warning Wrong handling expects to raise a danger resulting in death or serious injury of the operator C...

Страница 3: ...sassembling repairing and modifying the pump shall be limited to a repair technician There is a possibility of injury caused by electric shock ignition abnormal functioning trouble etc Before entering...

Страница 4: ...nt or by leakage of enclosed liquid from mechanical seal Do not use the pump at an important facility computer cooling apparatus cooling apparatus for refrigerator etc Since machining oil rubber relea...

Страница 5: ...the nameplate Specifically care shall be paid on the frequency 50 Hz or 60 Hz Caution Do not operate a pump of 50Hz at 60Hz The operation at wrong frequency induces pump break caused by excess pressur...

Страница 6: ...clusion of foreign matter Do not use the pump at facilities for organisms fish farm fish preserve aquarium etc There is a possibility of extinction of organisms caused by leak current or by leakage of...

Страница 7: ...side Ceramics carbon sliding material at motor side NBR rubber material Turbine oil ISO VG 32 Motor 1 2 Model number of poles Thermal class Phase frequency voltage current Built in protective device D...

Страница 8: ...erval depending on the use environment Depending on the use environment there may be generated rust at threaded sections machined sections with rust proof coating rust proofing sections etc 1 On trans...

Страница 9: ...his will not happen 13 Models DLA and DLJ will undergo automatic alternate operation only when they are paired Position the floats for these automatic alternate operation pumps DLJ as shown in Fig 5 T...

Страница 10: ...needs to be provided in the final installation It is recommended to use a circuit breaker as main breaker that is suitable for isolation according to appropriate legal standard EN60947 2 and is equip...

Страница 11: ...el E among the four lines as shown in Fig 7 Never connect the Green and Yellow stripe cord or the Green cord to the power source The grinding shall be surely conducted conforming to the Technology Sta...

Страница 12: ...ition or at near the operable minimum water level the Auto cut in the motor is actuated If the situation is repeated the pump life becomes short Once the Auto cut is actuated the motor does not start...

Страница 13: ...the pumps are now ready for operation Note Operate the pump at a discharge rate suitable for the facilities Operation at excessively small or large capacity causes noise and vibration and consumes unn...

Страница 14: ...hin the limit of pump rating the pump may have caught foreign matter 2 If the discharge rate showed a sudden decrease foreign matter may have clogged the suction opening 2 Regular inspection 1 Once a...

Страница 15: ...t every disassembly for inspection Every 20000 cycles of operation Every 100000 cycles of operation Expected replacement time One year or 6000 hours of total operating hours either of shorter one Once...

Страница 16: ...and water to a container Then clean the inside the leakage detector s chamber and motor chamber and replace the mechanical seal as well as gaskets and O rings Leakage Detector Contact rating AC280V 0...

Страница 17: ...ace the mechanical seal Liquid quality and operation conditions need to be reviewed Replace the mechanical seal Pumping not effected or insufficient pumping capacity Pump running in reverse rotation G...

Страница 18: ...L SEAL 1 SET 811 SUBMERSIBLE CABLE 1 115 1 O RING 1 814 MOTOR FRAME 1 115 2 O RING 1 816 BRACKET 1 115 3 O RING 1 817 BRACKET 1 117 1 GASKET 1 830 SHAFT 1 117 2 SEAL WATER 1 849 1 BALL BEARING 1 120 1...

Страница 19: ...without contacting with the suction cover Then enter the operation of the pump 11 Limited Warranty EBARA Corporation warrants to the original retail purchaser Customer the followings 1 This warranty v...

Страница 20: ...uires about the pump please contact EBARA Singapore Ebara Engineering Singapore Pte Ltd Website www ebara com sg E mail ebaranet singnet com sg Malaysia Ebara Pumps Malaysia Sdn Bhd Website www ebara...

Отзывы: