ROUTINE MAINTENANCE 

To  ensure  continued  full  efficiency  of  the  dehumidifier,  maintenance 
procedures should be performed as follows: 

1.

Clean the surface of the evaporator and condenser coils by blowing
the  dirt  out  from  behind  the  fins  with  compressed  air.  Hold  the
nozzle of the air hose away from the coil to avoid damaging the fins.
Alternatively, vacuum clean the coils.

2.

Check that the fan is firmly secured to the motor shaft and that the
fan rotates freely.  

The fan motor is sealed for life and therefore

does not need oiling.

3.

To  check  the  refrigerant  charge,  run  the  unit  for  15  minutes  and
briefly remove the top cover.  The evaporator coil should be evenly
frost  coated  across  its  surface.    At  temperatures  above  78

°

F,  the

coil may be covered with droplets of water rather than frost.  Partial
frosting  accompanied  by  frosting  of  the  thin  capillary  tubes,
indicates  loss  of  refrigerant  gas  or  low  charge.    During  this
inspection,  check  visually  to  ensure  that  the  pump  rollers  are
turning.

4.

Check all wiring connections.

5. To check the operation of the defrost system, switch the machine on

and leave it running for approximately 55 minutes.  The machine will
then  enter  “Hot  Gas”  defrost  mode  for  approximately  5  minutes
before  returning  to  normal  operation.    If  the  unit  will  not  defrost,  the
printed circuit timer board may be defective or the by-pass valve may
be inoperable.

I

F ANY OF THE PRECEDING PROBLEMS OCCUR

,

 CONTACT THE 

E

BAC

S

ERVICE 

C

ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO

PREVENT PERMANENT DAMAGE

.

WARNING: 

ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN 

DISCONNECTED BEFORE CARRYING OUT ROUTINE 

MAINTNENANCE ON ITEMS 1, 2, 3, 4 & 5 

WARNING:

 

DO NOT STEAM CLEAN REFRIGERATION COILS 

E B A C    K O M P A C T    R E S T O R A T I O N    D E H U M I D I F I E R 

Pure n Natural Systems  |  purennatural.com  |  1-800-237-9199

Содержание KOMPACT

Страница 1: ...9 Drawing TPC303 Issue 7 Date 03 10 12 KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL E B A C K O M P A C T R E S T O R A T I O N D E H U M I D I F I E R Pure n Natural Systems purennatural com 1 800...

Страница 2: ...ONTENTS Item Description Quantity 10240KP US Dehumidifier 1 3086144 Quick release hose coupling 1 3944110 PVC Tube 3 8 I D 7 8M TPC303 Manual 1 E B A C K O M P A C T R E S T O R A T I O N D E H U M I...

Страница 3: ...asses through the hot condenser coil where it is reheated using the same energy removed during the cooling phase plus the additional heat generated by the compressor The air is therefore discharged fr...

Страница 4: ...ial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label MODEL 10240KP US HEIGHT 24 610mm WIDTH 20 508mm DE...

Страница 5: ...ve 78 F frost and or droplets of condensed water should cover the entire evaporator coil F After continuous running time of approximately 55 minutes unit will enter Hot Gas defrost mode for several mi...

Страница 6: ...rost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge During this inspection check visually to ensure that the pump rollers are turn...

Страница 7: ...and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing further loss of refrigerant gas 3 The refrigerant compressor f...

Страница 8: ...3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass valve 1...

Страница 9: ...1107 1 6 Capillary Tube 3014251 48 7 Solenoid Valve 3020814 1 8 Filter Dryer 3020901 1 9 Compressor 3022169 1 10 Solenoid Coil 3030421 1 11 Capacitor 3030908 1 12 Terminal Block 3031460 1 13 Fan Motor...

Отзывы: