CD100 OWNERS MANUAL
Drawing No. :- TPC112
Issue :-
1
Date :-
20/06/03
ROUTINE MAINTENANCE
WARNING:
ENSURE THAT THE POWER CORD TO THE MACHINE
HAS BEEN DISCONNECTED BEFORE CARRYING OUT
ROUTINE MAINTENANCE ON ITEMS 1, 2, 4, 5, AND 6.
To ensure continued full efficiency of the dehumidifier, maintenance procedures should be
performed as follows:
Removal of the cover is achieved by means of four screws at the sides of the unit at base level.
With the cover removed all maintenance can be carried out.
1.
Clean the surface of the evaporator and condenser coils by blowing the dirt out from
behind the fins with compressed air. Hold the nozzle of the air hose away from the
coil (approx 6”) to avoid damaging the fins. Alternatively, vacuum clean the coils.
WARNING:
DO NOT STEAM CLEAN REFRIGERATION COILS.
2.
Check that the fan is firmly secured to the motor shaft and that the fan rotates freely.
THE FAN IS SEALED FOR LIFE AND DOES NOT NEED LUBRICATING.
3.
To check the refrigerant charge, run the unit for 20 minutes (with humidistat set to
maximum) and briefly remove the cover. The evaporator coil should be evenly frost
coated across its surface. At temperatures above 25
°
C, the coil may be covered with
droplets of water rather than frost. Partial frosting accompanied by frosting of the
thin capillary tubes, indicates loss of refrigerant gas or low charge.
4.
Check all wiring connections.
I
F ANY OF THE PRECEDING PROBLEMS OCCUR
,
CONTACT THE
E
BAC
S
ERVICE
C
ENTER PRIOR TO
CONTINUED OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE
.