CD100 OWNERS MANUAL 

Drawing No.  :-  TPC112 
Issue :- 

Date :- 

20/06/03

 

INTRODUCTION

 

 

Dehumidifiers remove moisture from the air that is circulating through the unit. 
The resulting reduction of relative humidity helps prevent rust, rot, mould, mildew and 
condensation within the room, or other enclosed spaces where the dehumidifier is used. 
A dehumidifier consists of a motor-compressor unit, a refrigerant condenser, an air circulating 
fan, a refrigerated surface, a means of collecting and disposing the condensed moisture and a 
cabinet to house these components. 
The fan draws air through the refrigerated surface and cools it below its dew point, removing 
moisture which is collected and led away. The cool air then passes the hot condenser, where it is 
reheated. With the addition of other radiated heat the air is discharged into the room at a higher 
temperature but lower relative humidity than when the air entered the unit. Continuous 
circulation of the room air through the dehumidifier unit gradually reduces the relative humidity 
in the room. 
 
 
The CD100 dehumidifier is a rugged reliable drying unit designed to operate effectively over a 
broad range of temperature and humidity conditions. A powerful and reliable active hot gas 
defrost system, controlled by an electronic timer, guarantees positive de-icing and thereby 
optimising operation at low temperatures. 
The unit incorporates a welded steel chassis and is finished in vinyl coated steel covers for 
resilience to damage caused by rough handling.  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание CD100

Страница 1: ...ER S MANUAL Ebac Commercial Ltd St Helens Trading Estate Bishop Auckland Co Durham DL14 9AD Telephone 01388 664400 Fax 01388 662590 Website www ebacuk com Ebac Industrial Products 704 Middle Ground Bo...

Страница 2: ...ure which is collected and led away The cool air then passes the hot condenser where it is reheated With the addition of other radiated heat the air is discharged into the room at a higher temperature...

Страница 3: ...S MODEL CD100 HEIGHT 400mm WIDTH 900mm DEPTH 500mm WEIGHT 50 Kg AIRFLOW 510 M3 hr POWER SUPPLY UK 220V 240V 1 ph 50Hz 60Hz USA 110V 120V 1 ph 50Hz 60Hz POWER 1 2kW max FINISH Vinyl coated steel REFRIG...

Страница 4: ...in anyway WIRING Connect the power mains cable to a 13 Amp power supply As follows Brown Live Blue Neutral Green Yellow Earth ground DRAINAGE Connect a 15mm inside diameter hose to the water outlet pi...

Страница 5: ...ning for 20 minutes the coils located above the drain tray will be evenly coated in frost If the ambient temperature is above 25 C the coils will be covered in water 4 After the machine has been runni...

Страница 6: ...ear to be functioning correctly then refer to the repairs section Warnings Due to the high pressures within the refrigeration circuit under no circumstances must direct heat be applied to the evaporat...

Страница 7: ...he coil approx 6 to avoid damaging the fins Alternatively vacuum clean the coils WARNING DO NOT STEAM CLEAN REFRIGERATION COILS 2 Check that the fan is firmly secured to the motor shaft and that the f...

Страница 8: ...e of the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak ca...

Страница 9: ...efrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty Timer 2 Faulty bypass timer 1 Contact the...