9 Technical data
9.5 Interfaces
72
Touch display XV-102
10/2020 MN04802004Z-EN
Eaton.com
9.5.2
SmartWire-DT Master
9.5.2.1
POW/AUX (power supply interface for SmartWire-DT)
Property
XV-102
Supply voltage U
Aux
(control voltage for contactor coils)
Operational voltage
Rated operating voltage
24 VDC
Permissible voltage
Effective:
20.4…28.8 V DC (rated operating voltage -15 % /
+20 %)
Input voltage residual ripple
Max. 5 %
Protection against polarity reversal
Yes
Current
In accordance with DIN VDE 0641, Part 11
and IEC/EN 60898
Max. 3 A
1)
In accordance with UL 508
and CSA-22.2, No. 14
Max. 2 A
1)
Short-circuit rating
No, external protection required
(e.g. FAZ Z3,
Heat dissipation
Normally 1 W
Potential isolation
No
Rated operating voltage of
24 V DC slaves
Normally U
Aux
- 0.2 V
Supply voltage U
Pow
(for SmartWire-DT slaves)
Specifications for connection to supply voltage
Rated operating voltage
24 VDC
Permissible voltage
Effective:
20.4…28.8 V DC (rated operating voltage -15 % /
+20 %)
Input voltage residual ripple
Max. 5 %
Protection against polarity reversal
Yes
Current
Max. 0.7 A
Overload proof
Yes
Inrush current and length
12.5 A/6 ms
Heat dissipation at 24 VDC
1.0 W
Potential isolation between U
Pow
and
15 V SmartWire-DT supply voltage
No
Bridging voltage dips
10 ms
Содержание XV100
Страница 1: ...Manual XV 102 Touch display 10 2020 MN04802004Z EN ...
Страница 6: ...Content 4 Touch display XV 102 10 2020 MN04802004Z EN Eaton com ...
Страница 22: ...3 Safety regulations 3 4 Device specific hazards 20 Touch display XV 102 10 2020 MN04802004Z EN Eaton com ...
Страница 24: ...4 Operating and indication elements 4 1 Overview 22 Touch display XV 102 10 2020 MN04802004Z EN Eaton com ...
Страница 60: ...6 Operation 6 4 Inserting and removing the SD card 58 Touch display XV 102 10 2020 MN04802004Z EN Eaton com ...
Страница 64: ...7 Maintenance and repairs 7 4 Troubleshooting 62 Touch display XV 102 10 2020 MN04802004Z EN Eaton com ...