5 Installation
5.3 Interfaces
44
Touch display XV-102
10/2020 MN04802004Z-EN
Eaton.com
5.3.10
Profibus
The Profibus interface is
not
galvanically isolated.
Tab. 20 Pin assignment of the Profibus interface
CAUTION
Non-galvanically-isolated interfaces
The device may be damaged by potential differences.
The GND terminals of all bus modules must be connected.
Fig.. 24 Profibus interface (9-pin, D-Sub, female, UNC)
Pin
Signal
Configuration
1
-
nc
2
-
nc
3
B
EIA RS 485 line B
4
RTSAS
Output for controlling a repeater
5
M5EXT
Output 0 V for external termination
6
P5EXT
Output 5 V for external termination
7
-
nc
8
A
EIA RS 485 line A
9
-
nc
Pin 6 (5 V) must not be used as a power supply for external devices.