8
Appendix
InstructIon manual
MN050011EN August 2022 www.eaton.com
Technical data
Ambient conditions
Description
specification
Storage temperature
–20 to +85 °C
Operating ambient temperature
0 to +55 °C
Humidity
0–95 %, noncondensing
EMC interference immunity
As per EN 61000-6-2 (industrial environment)
EMC emitted interference
As per EN 61000-6-4 (industrial environment)
Vibration resistance
EN 60068-2-6
3.5 mm of 5–8.4 Hz
1 g of 8.4–150 Hz
Mechanical shock resistance
EN 60068-2-27 15 g
Protection type
EN 60529
IP20
Power supply
specifications for connection to supply voltage
Specifications for connection to supply voltage Ue
V
18–30 V
DC
Residual ripple of input voltage
%
≤ 5
Protection against polarity reversal
No
Overload proof
Yes
Supply current X6 (typ.)
200 mA
a
The device must be powered with a galvanically isolated power supply
with a rated voltage of 24 Vdc. A UL 249 fuse (maximum 4 A) must be
installed between the power supply and the end device.
Cable cross-sections
cable cross-sectional areas
Xn-332-…
0.39 inch (10 mm)
Solid
mm
2
0.2–1.5
0.39 inch (10 mm)
Flexible with
uninsulated ferrule
mm
2
0.2–1.5
0.39 inch (10 mm)
Flexible with
insulated ferrule
mm
2
0.2–0.75
Ferrule d
mm
≤ 2.8
AWG
24–16
Strip length
mm
10
Additional information
General
Xn-332-…
Imprintable label
MF 10/5 CABUR MC NE WS (Weidmüller)
Further reading and links
For more information on additional devices and modules,
please visit the following links.
Product information
For up-to-date information, please consult the product page:
Download Center—documentation
You can find the documents on the Download Center
documentation page by entering the document name.
http://www .eaton .eu/documentation
File type
title
Designation
Mounting instruction
XN-332-5ETH-UMS
IL050026ZU
Mounting instruction
XN-312-GW-CAN
IL050017ZU
Mounting instruction
XN-312-GW-EC
IL050025ZU
Mounting instruction
XC300
IL050018ZU
Manual
XN-312-GW-CAN
MN050003
Manual
XN-312-GW-EC
MN050010
Manual
XN300 slice modules
MN050002
Manual
XC300
MN050005
d