4 Integrating the Module in CANopen
Object description
62
XI/ON: XN-1RS232
09/2011 MN05002013Z-EN
www.eaton.com
Table 26: Meaning of the data bits
Parameter
designation
Value
Description
DisableDiagnos-
tics
(Diagnostics)
0
Diagnostics activated = 0
Diagnostics deactivated = 1
This controls the separate fieldbus-specific diagnostics
signal - not the diagnostics signal embedded in the
process input data (object 5601
hex
).
1*
DisableR-
educedControl
0
The diagnostics messages are not part of the process
input data (object 5601
hex
). Bytes1 to 7 can therefore
be used for the user data.
1
The diagnostics messages are contained in byte 1 of
the object 5601
hex
(irrespective of “DisableDiagnos-
tics”). Byte 0 contains the status and control byte.
Bytes 2 to 7 are available for the user data.
The structure of the object 5602
hex
is also changed by
this setting. At the location of the first data byte, byte 1
of the object 5602
hex
contains a byte with two control
bits. These can initiate a clearing of the receive and
transmit buffer.