3 Integrating the Module in DeviceNet
RS232 Module Class (VSC114)
56
XI/ON: XN-1RS232
09/2011 MN05002013Z-EN
www.eaton.com
128
(80
hex
)
ACTIVE
MODE
G/S
BOOL
0 = "1byte ctrl/status header":
The diagnostics data is not part of
the process input data. The user
data section is 7 bytes.
1 = "2bytes ctrl/status header":
The diagnostics data is part of the
process input data. The user data
section is 6 bytes.
129
(81
hex
)
BIT RATE
G/S
ENUM
USINT
Bit transmission rate
0 = "<reserved>"
1= 300 bit/s
2 = 600 bit/s
3 = 1200 bit/s
4 = 2400 bit/s
5 = 4800 bit/s
6 = 9600 bit/s
7 = 14400 bit/s
8 = 19200 bit/s
9 = 28800 bit/s
10 = 38400 bit/s
11 = 57600 bit/s
12 = 115200 bit/s
13 to 15 = "<reserved>"
130
(82
hex
)
DISABLE
DIAGNOS-
TICS
G/S
BOOL
0 = "released": Diagnostics acti-
vated.
1 = "blocked": Diagnostics deacti-
vated:
This controls the separate fieldbus-
specific diagnostics signal - not the
diagnostics signal embedded in the
process input data..
Attr.
no.
dec.
(hex.)
Attribute
name
Access
Type
Description