3. Installation
3.4 Preparing the device for operation
3.4.1 Power supply - electrical connection
signal
Configuration
0 V
+24 V DC
+
Specifications for connection to supply voltage
+ 24 VDC SELV (safety extra low voltage)
FE
Connection Functional earth
–
Supply voltage 0 V
Tab. 4: Configuration Plug connector MSTB 2.5/3-ST-5.08
Specifications for connection to 24 VDC supply voltage
Copper conductor
60° / 70°C
Cross-section
min. 0.75 mm
2
/ max. 2.5 mm
2
(drain wire or conductor)
min. AWG18 / max. AWG12
Tightening torque
0.6 ... 0.8 Nm (5 ... 7 lb-in)
for the screws on the Plug connector MSTB 2.5/3-ST-5.08
Strip length
7 mm
Tab. 5: Specifications for connection to 24 VDC supply voltage
Power supply
+24 V DC
0 V
U
e
= 24 V DC
(19.2 - 30 V DC SELV)
I
e
= ...
0 V +24 V DC
0.6 - 0.8 Nm
(5 - 7 lb-in)
FE
Fig. 6: Connecting the screw terminals on the Plug connector MSTB 2.5/3-ST-5.08