3. Installation
3.1 Prerequisites for the location of use
Ventilation diagram
Clear Zone
a
a
b
b
c
Fig. 3: Cooling air
circulation
Fig. 4: Mounting distance
l
Make sure that there will be enough volume for air changes inside the control cab-
inet, etc.
The specified clearance around the XH-303 HMI Web Panel is: a, b, c ≧ 30 mm
(1.18")
l
If you will be installing the XH-303 HMI Web Panel in complex systems together
with other assemblies, you must ensure that there will be enough air circulation in
order to prevent overheating.
Ambient temperature with natural convection: ϑ 0°C (32°F) ≦ T ≦ 50°C (122°F)
The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the XH-303 as necessary for design verification
in accordance with IEC EN 61439.
3.1.1.3 Criteria for the installation position
The XH-303 are intended to be flush mounted in control cabinets, control panels, or
control consoles.
l
XH-303 units can be installed in landscape or portrait mode.
l
If no forced ventilation is being used, the device must not be mounted at an angle
⍺
of more than ±α ≦ 45° relative to its fully vertical position.
An angle
⍺
greater than 10° for the XH-303-15-A10-A00-2B is only permissible with
a reduced maximum ambient temperature of 45 °C.
l
l
The enclosure material must be thick enough
2 mm (0.08") ≦ d ≦ 5 mm (0.2")
XH-303
09/22 MN048029EN Eaton.com
31
Содержание XH-303
Страница 1: ...Manual 09 22 MN048029EN XH 303 HMI Web Panel Manual...
Страница 4: ......
Страница 93: ...W Web Config App 48 Weight 82 XH 303 09 22 MN048029EN Eaton com 93...