4.2.3 Baud Rates
Dipswitches 11 and 12 of dipswitch S1 (accessed on the
side of the URTDII) set the Modbus baud rate. Table 7
shows the setting definitions:
Table 7, Baud Rate Selection Settings
Baud Rate
Dipsw11
Dipsw12
9600 Baud
OFF
OFF
19200 Baud
OFF
ON
38400 Baud
ON
OFF
115200 Baud
ON
ON
Actual Value Objects
Units
No. of
Reg.
Register Number
(Decimal)
Register Number
(Hexadecimal)
Category
Name
IEEE Float
Fixed Point
IEEE Float
Fixed Point
Fixed Point
Scale Factor
Fixed Point
Sign Factor
Product ID
Product ID
2
404718
406254
126E
186E
1
Signed
Motor winding 1
°C
2
404740
406276
1284
1884
1
Signed
Motor winding 2
°C
2
404742
406278
1286
1886
1
Signed
Motor winding 3
°C
2
404744
406280
1288
1888
1
Signed
Motor winding 4
°C
2
404746
406282
128A
188A
1
Signed
Motor winding 5
°C
2
404748
406284
128C
188C
1
Signed
Temperature
Motor winding 6
°C
2
404750
406286
128E
188E
1
Signed
Motor bearing 1
°C
2
404752
406288
1290
1890
1
Signed
Motor bearing 2
°C
2
404754
406290
1292
1892
1
Signed
Load bearing 1
°C
2
404756
406292
1294
1894
1
Signed
Load bearing 2
°C
2
404758
406294
1296
1896
1
Signed
Auxiliary 1
°C
2
404760
406296
1298
1898
1
Signed
Auxiliary 2
°C
2
404762
406298
129A
189A
1
Signed
Case
°C
2
404764
406300
129C
189C
1
Signed
4.2.4 Register Map
The following tables show the addresses and data values
contained in each application category with a base address
of 0x00.
Table 8, Last Reset Status Definitions
Cause of Last Reset
Holding Register Value
Power Up Reset
0x00
Software Reset
0x01
Wake Up Reset
0x02
RTC Reset
0x03
Low Voltage Detect Reset
0x04
Watchdog Reset
0x05
Table 9, Modbus Register Map
9
Universal Resistance Temperature IL02602013E
Detector (RTD) Module II
November 2010
IL02602013E - November 2010 - www.eaton.com