background image

3.2 RTD Wiring

Each RTD must be wired to the URTDII, as shown in Figure 

4. The following guidelines must be observed:
Use only one type of RTD (10 ohm copper, 100 ohm nickel, 

100 ohm platinum, or 120 ohm nickel) for each RTD group: 

motor winding, motor bearing, load bearing and auxiliary. 

For example, you cannot monitor one 10 ohm copper motor 

bearing RTD and one 120 ohm nickel motor bearing RTD. 

However, you can monitor 10 ohm copper winding RTDs 

and 100 ohm nickel motor bearing RTDs.
1. Use #18 three-conductor, stranded, twisted, copper wire 

to connect the RTD to the URDTII. 
2. Connect three conductors from the RTD to the URTDII.  

(Two return wires must be connected together). Where the 

motor has only two leads from the RTD, connect two of the 

three conductors together at one of the leads. Make this 

connection as close to the RTD as possible (see Figure 5). 

If only two conductors are connected between the RTD and 

the URTDII, the device will not operate correctly.
3. Connect the cable shield and drain wires to the appropri-

ate terminal on the URTDII. At the opposite end, cut the 

shield and drain wire short and tape them, to prevent short 

circuits. 

Do not connect this wiring at the RTD end.

otee:

N

4. If one or more of the 12 possible RTD inputs on the 

module are not used, they can be left open or jumpered out 

without affecting the operation of the protective devices.

3.3 Wire Routing

Wire routing is divided into two types: High voltage (440 

Vac and higher) and low voltage (120 Vac and DC signals). 

The control and the RTD wiring are low voltage lines. 

Maintain at least 45 to 60 cm (1.5 to 2 feet) between high 

voltage and low voltage conductors. Never route high volt-

age and low voltage lines in the same raceway.

If 

otee:

N

a fiber optic link is used, run the optic cable in the 

same cable tray as high voltage conductors.

3.4 Protective Device Connections

The URTDII can be connected to a protective device using 

fiber optic cable. The fiber optic cable may be no longer 

than 122 meters (400 feet) in length. This cable is available 

from Hewlett-Packard using style number HFBR-ELS-xxx. 

where xxx is the length of the cable in meters. This is plas-

tic fiber optic cable that has connectors already attached at 

each end. Equivalent cable and connectors may be used. 

Table 3, DIP Switch Settings 

A. Motor Winding RTD

C. Load Bearing RTD

RTD Type 

Switch Settings 

RTD Type 

Switch Settings

1

2

5

6

100 Ohm Platinum 

ON

ON

100 Ohm Platinum 

ON

ON

100 Ohm Nickel 

OFF

ON

100 Ohm Nickel 

OFF

ON

120 Ohm Nickel 

ON

OFF

120 Ohm Nickel 

ON

OFF

10 Ohm Copper

OFF

OFF

10 Ohm Copper

OFF

OFF

B. Motor Bearing RTD

D. Auxiliary RTD

RTD Type

Switch Settings

RTD Type

Switch Settings

3

4

7

8

100 Ohm Platinum 

ON

ON

100 Ohm Platinum 

ON

ON

100 Ohm Nickel 

OFF

ON

100 Ohm Nickel 

OFF

ON

120 Ohm Nickel 

ON

OFF

120 Ohm Nickel 

ON

OFF

10 Ohm Copper

OFF

OFF

10 Ohm Copper

OFF

OFF

4

IL02602013E

                                                            

Universal Resistance Temperature 

November 2010  

                                                                          

Detector (RTD) Module II 

 

    

   IL02602013E - November 2010 -  www.eaton.com

         

                      

Содержание URTDII

Страница 1: ...Table of Contents 1 0 Introduction 2 0 Assembly Drawing 3 0 Installation 4 0 Communications Universal Resistance Temperature Detector Module II Instruction Leaflet IL02602013E Effective November 2010...

Страница 2: ...t its information to a protective device using a fiber optic link It can be mounted remotely up to 122 meters 400 feet from the protective device when using the fiber optic link The URTDII can also be...

Страница 3: ...ssembly on the module enables programming for the specific application Figure 2 shows the arrangement of the DIP switches in the assem bly They provide four selection groupings that you must set durin...

Страница 4: ...Wire routing is divided into two types High voltage 440 Vac and higher and low voltage 120 Vac and DC signals The control and the RTD wiring are low voltage lines Maintain at least 45 to 60 cm 1 5 to...

Страница 5: ...ommended 2 RTDs must not be grounded at the motor and no common connections between RTDs 3 should be made at the motor A suitable earth ground should be connected to J10B 4 J10B 11 J 10B 18 J2 4 J2 11...

Страница 6: ...otes Connect cable shield at URDTII terminals only Cut shield short at motor end 1 and use shrink tubing or electrical tape to insulate RTDs must not be grounded at the motor and no common connections...

Страница 7: ...PWR IN 2 PWR IN 1 2 1 J10A Figure 6 Fiber Optic Connection between MP 4000 and Universal RTD Module II To Power Supply Terminal Block Power J10A AC Power Supply DC Power Supply 1 Line Positive 2 Neut...

Страница 8: ...switches 1 to 8 represent the binary address of the URTDII Dipswitch 1 is the most significant address bit and dipswitch 8 in the least significant bit Table 6 shows an abbreviated example of the addr...

Страница 9: ...winding 5 C 2 404748 406284 128C 188C 1 Signed Temperature Motor winding 6 C 2 404750 406286 128E 188E 1 Signed Motor bearing 1 C 2 404752 406288 1290 1890 1 Signed Motor bearing 2 C 2 404754 406290 1...

Страница 10: ...com 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No IL02602013E November 2010 PowerChain Management is a registered trademark of Eaton Corporation All other trademarks are pro...

Отзывы: