4. HANDLING
Please follow the instructions in order to move the transformer.
• Transformer can moved by means of cylindrical rollers in manual handling as it is shown in
the figure 1.
• If crane or lift truck is necessary according to distance and power of transformer, only use
lifting lugs on the cover as it is shown in the figure 2 and 3.
• Transformer must never be lifted at the lower side of the cooler fins as it is shown in the
figure 4.
• Never use the bushings (high voltage (HV) or low voltage (LV) insulators) to guide the
transformer when moving it.
• During the transport or the handling, it is recommended to use only the special lifting eyes
and tow attachments. Angle between the laps has to be 60 degrees.
• Use suitable hook and rope which has enough length.
• The length of the ropes (H) must be greater than the distance between lifting lugs (L).
Fig. 1
Manual Handling
Fig. 2
Lifting Transformer
Fig. 3
Handling by means of bridge
crane and forklift truck
Fig. 4
Wrong handling!
WARNING:
The transformer can not be moved by pushing the cooling fins or radiators or tank.
Ulusoy Distribution Transformers Maintenance, Operation, Installation and Instruction Manual