38
No battery
Fault (Red) LED is Flash
1beep every 1 second
Code: A011
The batteries are disconnected.
Verify that all batteries are
properly connected.
If the condition persists,
contact your service
representative.
Bypass mode
Bypass (Orange) LED is
on.
Code: E060
An overload or a fault has
occurred, or a command has
been received and the UPS is in
Bypass mode
Equipment is powered but
not protected by the UPS.
Check for one of the
following alarms: over
temperature, overload or
UPS failure.
Power overload
Fault (Red) LED is Flash
2beep every 1 second
Code: A041
Power requirements exceed
the UPS capacity
Remove some of the
equipment from the UPS.
The UPS continues to
operate, but may switch to
Bypass mode or shut down
if the load increases.
The alarm resets when the
condition becomes
inactive.
UPS over temperature
Fault (Red) LED is On.
Beep continuous.
Code: F081
The UPS internal heat sink
temperature is too high or a
fan has failed.
At the warning level, the UPS
generates the alarm but
remains in the current
operating state.
If the temperature rises
another 2°C, the UPS transfers
to Bypass mode or Standby
mode.
Clear vents and remove
any heat sources. Allow
the UPS to cool. Ensure the
airflow around the UPS is
not restricted. Restart the
UPS.
If the condition continues
to persist, contact your
service representative.
ON Maintenance
Bypass
Bypass (Orange) LED is
on.
Code: A072
UPS was manually commanded
to switch to bypass and will
remain in bypass until
commanded out of bypass
Check the maintain bypass
switch status