19
Online mode
The UPS is operating
normally.
The UPS is powering and protecting the
equipment.
Battery mode
1 beep every 4
seconds
A utility failure has
occurred and the UPS is
on Battery mode.
The UPS is powering the equipment with
the battery power.
Prepare your equipment for shutdown.
End of backup time
1 beep every 1
seconds
The UPS is on Battery
mode and the battery is
running low.
This warning is approximate, and the
actual time to shutdown may vary
significantly.
Depending on the UPS load and number of
Extended Battery Modules (EBMs), the
"Battery Low" warning may occur before
the battery reaches 20% capacity.
High Efficiency
mode
The UPS is operating
on High Efficiency
mode.
Once the mains are loss or abnormal, the
UPS would transfer to Line mode or
Battery mode and the load is supplied
continuously.
1. The function could be enabled through
the LCD setting or the software
(Winpower, etc.)
2. It is reminded that the transfer time of
UPS output from HE mode to battery
mode is about 10ms. But it is still too long
for some sensitive load.
Bypass mode
Overload or fault has
occurred, or a
command has been
received, and the UPS
is in Bypass mode.
Equipment is powered but not protected
by the UPS.