8.2.
Coverage ratings
VAD performance is now stated as ‘real world’
coverage volume, rather than the old misleading
& often inconsistent figures of point intensity
(candela), circuit power (watts) or flash storage
energy (joules).
As a result, achieving a more relevant &
consistent performance is now more straight
forward, since the actual coverage volume, area
& distance of the VAD in an installation is stated.
The designators x & y are defined in EN54-23,
and define the coverage volume of the VAD.
7.3 Symphoni LX wall coverage for white & red flash
White flash
Red flash
Power setting
High
Low
High
Low
High
Low
High
Low
Flash rate setting
1Hz
0.5Hz
1Hz
0.5Hz
1Hz
0.5Hz
1Hz
0.5Hz
Width of room
y
(mounting
height
x
=2.4m)
7.5m
2.5
7.5
2.5
2.7
N/A
2.7
N/A
Floor coverage
56.25m
2
6.25m
2
56.25m
2
6.25m
2
7.3m
2
N/A
7.3m
2
N/A
Coverage volume
135m
3
15m
3
135m
3
15m
3
17.5m
3
N/A
17.5m
3
N/A
Current consumption @
24Vdc
25mA
15.5mA 15.5mA 9.5mA
24.5mA 14.5mA 14.5mA 10.5mA
8. Product Dimensions
Weight
GB Origin
Red Base LX
100G
●
White Base LX
100G
●