![Eaton SVX9000 Series Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/eaton/svx9000-series/svx9000-series_manual_4133346006.webp)
June 2006
6
For more information visit:
www.EatonElectrical.com
CA04000006E
SVX9000 Adjustable Frequency Drives
Open Drives
Catalog Number Selection
Table 4. Adjustable Frequency Drive Catalog Numbering System
���
All 230V Drives and 480V Drives up to 200 hp (IH) are only available with Input Option
1
(EMC Level H)
.
480V Drives 250 hp (IH) or larger are available
with Input Option
2
(EMC Level N). 480V Drives are available with Input Option
4
(EMC Level L). 575V Drives 200 hp (IH) or larger are only available
with Input Option
2
. 575V Drives up to 150 hp (IH) are only available with Input Option
4
(EMC Level L).
���
480V Drives up to 30 hp (IH) are only available with Brake Chopper Option
B
. 480V Drives 40 hp (IH) or larger come standard with Brake Chopper
Option
N
. 230V Drives up to 15 hp (IH) are only available with Brake Chopper Option
B
. 230V Drives 20 hp or larger come standard with Brake Chopper
Option
N
. All 575V Drives come standard without Brake Chopper Option (
N
).
Note:
N = No Brake Chopper.
���
480V Drives 250 hp (IH) and larger are available with enclosure style
0
(Chassis); 690V Drives 200 hp (IH) and larger are available with enclosure
style
0
(Chassis).
���
480V and 690V FR10 Freestanding Drives are available with enclosure style
1
(NEMA Type 1) and enclosure style
2
(NEMA Type 12). FR11 Freestanding
Drives only available with enclosure style
1
(NEMA Type 1).
���
Factory promise delivery. Consult Sales Office for availability.
Keypad
A
= Alphanumeric
S V X 0 1 0 A 1 – 4 A 1 B 1
Board Modifications
1
= Standard Boards
2
= Conformal (Varnished) Coating
���
Brake Chopper Options
���
N
= No Brake Chopper Circuit
B
= Internal Brake Chopper Circuit
Input Options
���
1
= 3-phase, EMC H
2
= 3-phase, EMC N
4
= 3-phase, EMC L
Options
Options appear in alphabetical order.
Extended I/O Card Options
B1
= 6 DI, 1 ext +24V DC/EXT +24V DC
B2
= 1 RO (NC/NO), 1 RO (NO), 1 Therm
B4
= 1 AI (mA isolated), 2 AO (mA isolated),
1 ext +24V DC/EXT + 24V DC
B5
= 3 RO (NO)
B8
= 1 ext +24V DC/EXT +24V DC, 3 Pt100
B9
= 1 RO (NO), 5 DI 42 – 240V AC Input
Communication Cards
CA
= Johnson Controls N2
CI
= Modbus TCP
CJ
= BACnet
CK
= Ethernet IP
C2
= Modbus
C3
= Profibus DP
C4
= LonWorks
C5
= Profibus DP (D9 Connector)
C6
= CanOpen (Slave)
C7
= DeviceNet
C8
= Modbus (D9 Type Connector)
D3
= RS-232 with D9 Connection
Product Family
SVX
= Open Drives
SPX
= Open Drives
FR10 & greater
Horsepower Rating
F07
= 3/4 hp
F15
= 1-1/2 hp
007
= 7-1/2 hp
010
= 10 hp
050
= 50 hp
125
= 125 hp
350
= 350 hp
700
= 700 hp
800
= 800 hp
900
= 900 hp
H10
= 1000 hp
H12
= 1200 hp
H13
= 1350 hp
H15
= 1500 hp
H16
= 1600 hp
H20
= 2000 hp
AFD Software Series
A
= Standard Software
Enclosure
������
0
= Chassis
1
= NEMA Type 1
2
= NEMA Type 12
Voltage Rating
2
= 230 (208 – 240) V
4
= 480 (380 – 500) V
5
= 575 (525 – 690) V