June 2006
12
For more information visit:
www.EatonElectrical.com
CA04000006E
SVX9000 Adjustable Frequency Drives
Open Drives
Modbus RTU Network Communications
The Modbus Network Card OPTC2 is
used for connecting the 9000X Drive as
a slave on a Modbus network. The
interface is connected by a 9-pin DSUB
connector (female) and the baud rate
ranges from 300 to 19200 baud. Other
communication parameters include an
address range from 1 to 247; a parity of
None, Odd or Even; and the stop
bit is 1.
Profibus Network Communications
The Profibus Network Card OPTC3 is
used for connecting the 9000X Drive as
a slave on a Profibus-DP network. The
interface is connected by a 9-pin DSUB
connector (female). The baud rates
range from 9.6K baud to 12M baud,
and the addresses range from 1 to 127.
LonWorks Network Communications
The LonWorks Network Card OPTC4 is
used for connecting the 9000X Drive
on a LonWorks network. This interface
uses Standard Network Variable Types
(SNVT) as data types. The channel
connection is achieved using a
FTT-10A Free Topology transceiver
via a single twisted transfer cable. The
communication speed with LonWorks
is 78 kBits/s.
CanOpen (Slave) Communications
The CanOpen (Slave) Network Card
OPTC6 is used for connecting the
9000X Drive to a host system. Accord-
ing to ISO11898 standard cables to be
chosen for CAN bus should have a
nominal impedance of 120
1
, and
specific line delay of nominal 5 nS/m.
120
1
line termination resistors
required for installation.
DeviceNet Network Communications
The DeviceNet Network Card OPTC7
is used for connecting the 9000X Drive
on a DeviceNet Network. It includes a
5.08 mm pluggable connector. Trans-
fer method is via CAN using a 2-wire
twisted shielded cable with 2-wire bus
power cable and drain. The baud rates
used for communication include 125K
baud, 250K baud and 500K baud.
Johnson Controls Metasys™ N2 Network
Communications
The OPTC2 fieldbus board provides
communication between the 9000X
Drive and a Johnson Controls
Metasys™ N2 network. With this con-
nection, the drive can be controlled,
monitored and programmed from the
Metasys system. The N2 fieldbus is
available as a factory installed option
and as a field installable kit.
Modbus/TCP Network Communications
The Modbus/TCP Network Card OPTCI
is used for connecting the 9000X Drive
to Ethernet networks utilizing Modbus
protocol. It includes an RJ-45 plugga-
ble connector. This interface provides
a selection of standard and custom
register values to communicate
drive parameters. The board supports
10 Mbps and 100 Mbps communica-
tion speeds. The IP address of the
board is configurable over Ethernet
using a supplied software tool.
BACnet Network Communications
The BACnet Network Card OPTCJ
is used for connecting the 9000X Drive
to BACnet networks. It includes a
5.08 mm pluggable connector. Data
transfer is Master-Slave/Token
Passing (MS/TP) RS-485. This interface
uses a collection of 30 Binary Value
Objects (BVOs) and 35 Analog Value
Objects (AVOs) to communicate drive
parameters. The card supports 9.6,
19.2 and 38.4 Kbaud communication
speeds and supports network
addresses 1 – 127.
Ethernet/IP Network Communications
The Ethernet/IP Network Card OPTCK
is used for connecting the 9000X Drive
to Ethernet/Industrial Protocol net-
works. It includes an RJ-45 pluggable
connector. The interface uses CIP
objects to communicate drive
parameters (CIP is “Common Indus-
trial Protocol”, the same protocol used
by DeviceNet). The board supports 10
Mbps and 100 Mbps communication
speeds. The IP address of the board is
configurable by Static, BOOTP and
DHCP methods.