background image

 Installation Instructions for the Sure-Lites SELIN Series Emergency Light

© 2017 Eaton

All Rights Reserved

Printed in USA

Impreso en los EE. UU.

Publication No. IB505060EN

Eaton

1000 Eaton Boulevard

Cleveland, OH 44122

United States

Eaton.com

Eaton is a registered trademark.

All trademarks are property   

of their respective owners.

Eaton es una marca comercial

registrada. Todas las marcas 

comerciales son propiedad de sus 

respectivos propietarios.

The SELIN Series Emergency Light is furnished with
a sophisticated low voltage battery dropout circuit
to protect the battery from over discharge after the
useful output has been reached .
Allow 24 hours recharge time after installation to
power failure for full load testing.

 

If LED heads or charge indicator LED does not illuminate,
check the following: 
1. Check AC supply-verify that unit has 24 hour AC supply.
2. Unit is shorted or battery is not connected.
3. Battery discharged. Permit unit to charge for 24 hours and 

If following the above trouble shooting hints does not solve your 

problem, contact your local Eaton Lighting representative for

then re-test.

assistance.

• Charge Circuit (LED three blink red) and lamp/LED failure (LED 

four blink red) will clear when the unit successfully passes a 
manual or automatic 30 second test. 

• LED Off -No power to unit, emergency mode. 

• LED Steady Green -Unit is fully charged and is float charging the 

battery to maintain readiness. 

• LED Green Pulse -Unit is in a 24 hour fast charge of the battery. 

• LED Two Blink Red -Battery has failed a capacity test, or the bat

-

tery is disconnected. See “Clearing Failure Codes” above. 

• LED Three Blink Red -Battery charge circuit has failed. See 

“Clearing Failure Codes” above. 

• LED Four Blink Red -Lamps have burned out, or on an EXIT/

Combo, 50% or more of the LEDs have failed. See “Clearing 
Failure Codes” above. 

• LED Steady Yellow -30 second test or 10 second quick test (Fast 

Charge only). 

• LED Blinking Yellow -90 minute test 

SURE-LITES

STEADY BLINK 

GREEN - FAST 

CHARGE

STEADY YELLOW - 

QUICK TEST

4 BLINK RED - LAMP / 

LED FAILURE

3 BLINK RED - CHARGE 

CIRCUIT FAILURE

STEADY BLINK YELLOW 

- 90 MINUTE TEST

STEADY GREEN - 

FULL / FLOAT 

CHARGE

2 BLINK RED - 

BATTERY FAILURE

OFF - EMERGENCY 

MODE / POWER OFF

Eagle Eye
Self-Diagnostics

Отзывы: