Installation Instructions for the Sure-Lites SELIN Series Emergency Light
© 2017 Eaton
All Rights Reserved
Printed in USA
Impreso en los EE. UU.
Publication No. IB505060EN
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Eaton es una marca comercial
registrada. Todas las marcas
comerciales son propiedad de sus
respectivos propietarios.
The SELIN Series Emergency Light is furnished with
a sophisticated low voltage battery dropout circuit
to protect the battery from over discharge after the
useful output has been reached .
Allow 24 hours recharge time after installation to
power failure for full load testing.
If LED heads or charge indicator LED does not illuminate,
check the following:
1. Check AC supply-verify that unit has 24 hour AC supply.
2. Unit is shorted or battery is not connected.
3. Battery discharged. Permit unit to charge for 24 hours and
If following the above trouble shooting hints does not solve your
problem, contact your local Eaton Lighting representative for
then re-test.
assistance.
• Charge Circuit (LED three blink red) and lamp/LED failure (LED
four blink red) will clear when the unit successfully passes a
manual or automatic 30 second test.
• LED Off -No power to unit, emergency mode.
• LED Steady Green -Unit is fully charged and is float charging the
battery to maintain readiness.
• LED Green Pulse -Unit is in a 24 hour fast charge of the battery.
• LED Two Blink Red -Battery has failed a capacity test, or the bat
-
tery is disconnected. See “Clearing Failure Codes” above.
• LED Three Blink Red -Battery charge circuit has failed. See
“Clearing Failure Codes” above.
• LED Four Blink Red -Lamps have burned out, or on an EXIT/
Combo, 50% or more of the LEDs have failed. See “Clearing
Failure Codes” above.
• LED Steady Yellow -30 second test or 10 second quick test (Fast
Charge only).
• LED Blinking Yellow -90 minute test
SURE-LITES
STEADY BLINK
GREEN - FAST
CHARGE
STEADY YELLOW -
QUICK TEST
4 BLINK RED - LAMP /
LED FAILURE
3 BLINK RED - CHARGE
CIRCUIT FAILURE
STEADY BLINK YELLOW
- 90 MINUTE TEST
STEADY GREEN -
FULL / FLOAT
CHARGE
2 BLINK RED -
BATTERY FAILURE
OFF - EMERGENCY
MODE / POWER OFF
Eagle Eye
Self-Diagnostics