Installation Instructions for the Sure-Lites SELIN Series Emergency Light
Connect the incoming wires to the fixture’s power
supply wires using the wire nuts provided.Conn
-ect the white wire to neutral. If using 120V,conn
-ect the black wire to the hot lead.If using 277V,
connect the orange wire to the hot lead.Cap
If remote lamps are to be connected, extend DC
circuit per article 700 and 720 of N.E.C. and con-
nect to yellow(-) and ) leads provided.
Connect battery leads to PCB. Lamps will ligh at
this time.
Replace cover
Turn on AC supply.Lamps will extinguish at this time.
Prepare conduit holes in enclosure at the desired
!
"
#
$
%
"
#
$
"
&
"
'
(
)
$
*
+
#
,
'
$
#
,
#
-
&
'
.
Conduit hubs and grounding adapters selected from Table 1 pro-
vide a means to comply with equipment grounding requirements.
location using preferred methods such as hole cut-
ter or hole saw (see table for hole size).When us-
ing the hole cutter, place the punch on the inside
of the enclosure and draw it through to the outside.
/
-
'
0
In order to guard against enclosure damage, the
conduit should be aligned so as to prevent un-
necessary stress on the enclosure walls.
1
2
3
4
5
6
Secure the conduit connector(hub)onto the conduit
and then secure conduit connector (hub) into the
prepared enclosure hole using connector locknut.
/
&
"
&
Replace the batteries as needed according to ambient conditions
However, we recommend that the equipment be tested regularly
in accordance with local codes.
NOTE: Servicing of any parts should be performed by
qualified service personnel.
For replacement battery ,PC board,see fixture
labels.
ʹΠΟΕΦΚΥ
΄ΚΫΖ
ʹΠΟΕΦΚΥ
ʹΠΟΟΖΔΥΠΣ
͙ΦΓ͚
ΣΠΦΟΕΚΟΘ
ͲΕΒΡΥΖΣ
ΠΝΖ͑΄ΚΫΖ
ʹΒΥΒΝΠΘ
ͿΦΞΓΖΣ
ʹΒΥΒΝΠΘ
ͿΦΞΓΖΣ
ΣΠΦΟΕ
ΈΚΣΖ͑ΒΟΘΖ
͢
ͣ
͓
ͤ
ͥ
͓
ͨ
ͩ
͓
͢
͢
ͩ
͓
ͥͪ͢͡͞Ϳ͢
ͥͪ͢͡͞Ϳͪ
ͥͪ͢͡͞Ϳͪ͢
ͥͪ͢͡͞Ϳͣ͡
ͥ͢͢͞͡
ͥͩ͢͞
΅ͲͳͽͶ͑͢
-
&
'
to the wall and/or junction box using installer
the unused lead.Secure the emergency light
supplied hardware.
BATTERY
Ni-Cd
BLACK
7
8
9
:
;
"
<
,
/
&
#
&
=
The SELIN series has an integrated time delay circuit that
allows them to remain in emergency mode 15 minutes after
power is restored. To activate the time delay, remove the
jumper on the circuit board labeled TDI/J1.
The Sure-Lites Eagle Eye Self Diagnostics is continuously
monitoring your emergency fixture, and will signal any failure
through the 3 color indicator LED.
>
?
@
?
A
B
C
D
E
A
@
?
F
>
0
When the unit is first powered up, it will go into a 24 hour fast
charge, indicated by the indicator LED pulsing green. Once the unit
has fully charged, it will perform a self calibration, after which the
LED will change to steady green, indicating the unit is fully charged
and float charging the battery to maintain readiness.
G
@
F
H
A
@
?
I
D
J
@
?
>
K
0
The unit will perform a battery capacity, lamp/LED, and charge cir
-
cuit test every 30 days for 30 seconds. During this time, the indica
-
tor LED will change to a steady yellow. It will perform a full battery
capacity (90 minute) test once per year. During this time, the indica
-
tor LED will change to a blinking yellow.
/
A
>
G
A
B
D
J
@
?
>
K
0
• 10 Second “Installation” test – Press and release the test button
once during fast charge (blinking green) to initiate a 10 second
quick test. The sign will switch to emergency mode for 10 sec
-
onds allowing the installer to verify proper installation of the unit,
and the LED indicator will turn solid yellow.
• 30 Second Test -Press and release the test button once during
float charge (steady green). The indicator LED will turn steady
yellow to indicate the unit is performing a 30 second test of the
batteries and lamps/LEDs.
• 90 Minute Test -Press and release the test button a second time
during a 30 second test (steady yellow) to change to a 90 minute
test. During this test, the LED indicator will change to blinking
yellow, and the circuit will perform a full battery capacity, charge
circuit, and LED test.
• Canceling Test – Press and release the test button during the 90
minute test (flashing yellow) to return the fixture to its original
state (fast charge or float charge).
"
B
D
A
E
?
>
K
!
A
?
B
G
E
D
"
F
L
D
J
· A battery failure (LED two blink red) can be cleared by replacing
the battery. Disconnecting the battery and AC power, or perform
-
ing a full 90 minute discharge, will reset the error code, however,
it will return if the battery is faulty.