 Installation Instructions for the Sure-Lites SELIN Series Emergency Light

 

Connect the incoming wires to the fixture’s power
supply wires using the wire nuts provided.Conn
-ect the white wire to neutral. If using 120V,conn
-ect the black wire to the hot lead.If using 277V,
connect the orange wire to the hot lead.Cap

 

    

If remote lamps are to be connected, extend DC

circuit per article 700 and 720 of N.E.C. and con-
nect to yellow(-) and ) leads provided. 

 

    

Connect battery leads to PCB. Lamps will ligh at

this time.

 

    

Replace cover

Turn on AC supply.Lamps will extinguish at this time.

Prepare conduit holes in enclosure at the desired

 

 

!

"

 

#

$

%

"

 

#

$

"

 

&

"

 

'

(

)

$

*

+

#

,

'

 

$

#

,

#

-

&

'

.

Conduit hubs and grounding adapters selected from Table 1 pro-
vide a means to comply with equipment grounding requirements. 

       location using preferred methods such as hole cut-
      ter or hole saw (see table for hole size).When us-
      ing the hole cutter, place the punch on the inside
      of the enclosure and draw it through to the outside.

/

-

 

'

0

In order to guard against enclosure damage, the
conduit should be aligned so as to prevent un-
necessary stress on the enclosure walls.

1

2

3

4

5

6

Secure the conduit connector(hub)onto the conduit

and then secure conduit connector (hub) into the
prepared enclosure hole using connector locknut.

/

&

"

&

Replace the batteries as needed according to ambient conditions
However, we recommend that the equipment be tested regularly 
in accordance with local codes. 

NOTE:                 Servicing of any parts should be performed by

qualified service personnel.
For replacement battery ,PC board,see fixture

labels.

ʹΠΟΕΦΚΥ

΄ΚΫΖ

ʹΠΟΕΦΚΥ

ʹΠΟΟΖΔΥΠΣ

͙͹ΦΓ͚

͸ΣΠΦΟΕΚΟΘ

ͲΕΒΡΥΖΣ

͹ΠΝΖ͑΄ΚΫΖ

ʹΒΥΒΝΠΘ
ͿΦΞΓΖΣ

ʹΒΥΒΝΠΘ
ͿΦΞΓΖΣ

͸ΣΠΦΟΕ

ΈΚΣΖ͑΃ΒΟΘΖ

͢

ͣ

͓

ͤ

ͥ

͓

ͨ

ͩ

͓

͢

͢

ͩ

͓

ͥͪ͢͡͞Ϳ͢

ͥͪ͢͡͞Ϳͪ

ͥͪ͢͡͞Ϳͪ͢
ͥͪ͢͡͞Ϳͣ͡

ͥ͢͢͞͡

ͥͩ͢͞

΅ͲͳͽͶ͑͢

 

-

&

'

 

to the wall and/or junction box using installer 

the unused lead.Secure the emergency light

supplied hardware.

BATTERY

    Ni-Cd

BLACK

7

8

9

:

;

"

<

,

/

&

#

&

=

The SELIN series has an integrated time delay circuit that 
allows them to remain in emergency mode 15 minutes after 
power is restored. To activate the time delay, remove the 
jumper on the circuit board labeled TDI/J1. 

The Sure-Lites Eagle Eye Self Diagnostics is continuously 
monitoring your emergency fixture, and will signal any failure 
through the 3 color indicator LED. 

>

?

@

?

A

B

 

C

D

E

A

@

?

F

>

0

When the unit is first powered up, it will go into a 24 hour fast 
charge, indicated by the indicator LED pulsing green. Once the unit 
has fully charged, it will perform a self calibration, after which the 
LED will change to steady green, indicating the unit is fully charged 
and float charging the battery to maintain readiness. 

G

@

F

H

A

@

?

I

D

J

@

?

>

K

0

The unit will perform a battery capacity, lamp/LED, and charge cir

-

cuit test every 30 days for 30 seconds. During this time, the indica

-

tor LED will change to a steady yellow. It will perform a full battery 
capacity (90 minute) test once per year. During this time, the indica

-

tor LED will change to a blinking yellow. 

/

A

>

G

A

B

D

J

@

?

>

K

0

• 10 Second “Installation” test – Press and release the test button 

once during fast charge (blinking green) to initiate a 10 second 
quick test. The sign will switch to emergency mode for 10 sec

-

onds allowing the installer to verify proper installation of the unit, 
and the LED indicator will turn solid yellow. 

• 30 Second Test -Press and release the test button once during 

float charge (steady green). The indicator LED will turn steady 
yellow to indicate the unit is performing a 30 second test of the 
batteries and lamps/LEDs. 

• 90 Minute Test -Press and release the test button a second time 

during a 30 second test (steady yellow) to change to a 90 minute 
test. During this test, the LED indicator will change to blinking 
yellow, and the circuit will perform a full battery capacity, charge 
circuit, and LED test. 

• Canceling Test – Press and release the test button during the 90 

minute test (flashing yellow) to return the fixture to its original 
state (fast charge or float charge). 

"

B

D

A

E

?

>

K

!

A

?

B

G

E

D

"

F

L

D

J

· A battery failure (LED two blink red) can be cleared by replacing 

the battery. Disconnecting the battery and AC power, or perform

-

ing a full 90 minute discharge, will reset the error code, however, 
it will return if the battery is faulty. 