300vac, L-E or L-N ) 

APPLICATIONS 

 

Primary power circuits 

 

Telecommunication Systems / Rectifiers 

 

Process and Control Systems  

 

Computer Systems / Medical Systems 

FEATURES 

 

Patented MTMOV technology   

 

( Failsafe thermal disconnect )

 

 

UL1449 ed3 Type 4 listed components

 

 

150kA, 2 mode, L-N or L-E

 

 

UL94-V0 ABS din rail mount housing

 

 

Din 43880 form factor 4 din wide  

 

 

Dry contact alarm 

 

LED visual indicators for protection, 
power and fault conditions. 

 

FUNCTIONAL DESCRIPTION 

The SPD150i is designed to protect single and three 
phase power systems against damage from surges 
and spikes caused by lightning and other electrical 
sources. The unit is intended for point of entry or 
main board protection and is connected in parallel 
with the power system via HRC fuses. 
  

This model ( SPD150i ) is designed for use in 
systems with a grounded neutral in L-N mode. If 
your system does not have a grounded Neutral or 
is of a different voltage, this model is NOT 
suitable. 

 

OPERATION 

Indicators - The operation status of the SPD150i is 
indicated by leds on the front panel. The ‘OK’ ( blue ) 
light indicates that power is applied to the SPD150i 
The ‘FAULT’ light ( red ) indicates that the surge 
protection circuitry is damaged and the unit should be 
replaced. The additional 3 leds ( blue ) indicate the 
status of each MOV element. When the fault indicator 
lights, the protection relay contacts change over. The 
power failure alarm will operate when mains voltage 
falls below 180VAC. 
  

 

PHYSICAL AND ELECTRICAL SPECIFICATIONS

 

Model 

SPD150i 

Number of ports 

1 Port 

Method of mounting 

Fixed. DIN Rail mount 

Input voltage – Uc 

220-300vac 1P, 380-

480vac 3P 

Maximum continuous voltage – 
MCOV 

320 L-N, L-E 

Temporary overvoltage - TOV 

350VAC L-N, 15 mins 

Service type 

TT, TN, TN C-S or any 1 or 

3phase system with a 

grounded neutral. 

Test classification (IEC61643-11) 

Class II 

Maximum over current protection 

125A 

Protection modes 

Line-Neutral, Line-Earth 

Inom 8/20us (Line-Neutral/Earth). 
Nominal surge life. 

60kA 

Imax 8/20us (Line-Neutral/Earth). 
Maximum surge level. 

120kA 

Residual voltage (Vpl) (Line-
Neutral/Earth). (Let through 
voltage) 

<1000v (3kA, 8/20us,       

( IEC61643-11) 

Safety disconnect 

Series thermal fusing on 

MOV’s 

External disconnector 
requirement 

Max 125A HRC fuse  

Terminations 

 Power 16mm

2

 

Alarms/indicators 

5 LED display, dry 

contact alarm relay 

output – 250VAC/32VDC, 

5A, 5kV isolation 

Enclosure  rating 

IP20 

Standards. Designed  in 
accordance with : 

IEC61643-11,  ANSI/IEEE 

C62.41 Cat A & B, 

AS1768-2007 Cat A & B, 

UL1449ed3 type 4 

Installation instructions 

Supplied with unit. 

Dimensions 

70W x 58D x 90H (mm)  

Weight 

200g 

Environment 

-10 to 60

C, 0 to 95%RH 

(non-condensing) 

Warranty 

5 years, workmanship 

and materials 