background image

 

 

Specifications are subject to change without notice. Copyright 2015 Eaton Industries, Mascot. NSW. 

Technical Specification SPD150i 

 Doc# 5100SPD150i Rev1 

Page 2 of 2 

INSTALLATION 

Refer to the following procedure to connect the 
SPD150i.

 

1. CHECK 

 

Always work safely-disconnect power before 
making connections. 

  All wiring must be carried out by suitably 

qualified personnel according to applicable 
standards. 

  For installation adjacent to an M.E.N. link, 

use the L-N mode. Insert insulated link as 
shown. 

  For installation remote from the M.E.N. link, 

use the L-E mode. Remove link. A separate 
N-E protector may be required. 

 

Always use correct size HRC fuses. 

  For services >125A use 125A HRC fuses. 

For services <125A use 1 step below service 
size. DO NOT USE AN MCB. 

 

Always use Gg or Gl rated fuses. Do not use 
delay types or semiconductor fuses. 

 

 

2. INSTALL 

 

Locate fuse position as close as possible to 
the Main Switch.

 

 

Install fuse holders or fuse switch.

 

  Locate suitable position for SPD ensuring 

adequate space for cables. Do not install 
above heat generating objects or any 
position exposed to weather. 

 

 

3. CONNECT 

  Connect wiring-refer to connection diagram 

on this page. Always use bootlace wire 
ferrules for lowest resistance to prevent 
damage to wire.

 

 Use suitably rated cable for power 

connections. Cable should be rated for 
operation at system voltage and be 4mm to 
16mm sq.

 

  Use shortest possible cables for all 

connections or protection will be reduced. 

  For alarm cables use cable rated at system 

voltage at between 0.5-1.5mm

2

 

 

3. NOTES 

  125A fuses are rated for maximum surge 

rating. 

 

  Wiring from fuse to SPD carries surge 

currents only. This means lower size cables 
can be used than service size rating.

 

  If using undersize cables we recommend 

double insulating same.

 

  It is recommended NOT to connect alarm 

contacts to AC mains circuits if possible, to 

prevent flashover from surges on AC line. 
Connect to a BMS or PLC if possible. 

 

  Do not perform an insulation resistance test 

on this unit as it contains voltage limiting 
components which may be damaged during 
testing. 

 
3. EARTHING 

  The main earth wire (from earth link on 

switchboard to ground rod or system ) MUST 
be at least 6mm dia or larger.

 

 

Earth connections from the unit to neutral or 
earth link MUST be as short as possible.

 

 

Failure to comply with the above points 
can result in improper operation of the 
unit and possible damage to the 
installation. 

 
L-N mode connections 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 
 
L-E mode connections 
 

 

 

Отзывы: