Xenon beacon - SM87HXB & SM87XBT

English

The safety function of the Beacon is to provide an inter-

mittent spherical visual warning light when the correct 

voltage is applied to the unit. The DC versions of the 

Beacon are designed to operate on a supply voltage 

tolerance of +/- 20%; the AC versions of the beacon are 

designed to operate on a supply voltage tolerance of 

+/- 10%.
The telephone initiate versions of the Beacon are not 

included in this safety manual.
Under No fault (Normal) Operating conditions the 

SM87HXB Beacon will provide a spherical visual warning 

light when required by the system.
Under fault conditions the failure mode of the Beacon is a 

failure to provide a spherical visual warning light. For the 

failure rate associated with this failure mode please refer 

to the table below.

Assessment of functional safety

The SM87HXB Call Point is intended for use in a safety 

system conforming to the requirements of IEC61508.
UL has conducted a Failure Modes Effect and Diagnostic 

Analysis (FMEDA) of the SM87HXB Beacon against the 

requirements of IEC61508-2 using a proof test interval of 

8760hrs.

The results are shown below and are based on Route 1

H

The Beacon is classed as a Type A device.

SM87HXb beacon

Safety Function of SM87HXB Beacon: 

‘To provide a spherical cycled visual warning light when energised’

Architectural 

constraints:

Type A

HFT=0

SFF= 73%

Proof Test Interval

=8760Hrs

MTTR = 8 Hrs

SIL2

Random hardware 

failures:

λ

DD

 = 0

λ

DU

 = 2.96E-07

λ

SD

 = 0

λ

SU

 = 8.12E-07

Probability of failure 

on demand:

PFD

AVG

=1.30E-03

(Low Demand Mode)

SIL2

Probability of 

Dangerous failure on 

safety function:

PFH = 2.96E-07
(High Demand 

Mode)

SIL2

Hardware safety 

integrity compliance

Route 1

H

Systematic safety 

integrity compliance

Route 1

S

Systematic Capability

SC2

Overall SIL-capability 

achieved

SIL 2 (Low Demand)

SIL 2 (High Demand)

     

     

     

     

     

     

     

     

     

     

Conditions of safe use

The following conditions apply to the installation, operation 

and maintenance of the assessed equipment. Failure to 

observe these may compromise the safety integrity of the 

assessed equipment.

1.  The user shall comply with the requirements given in 

the manufacturer’s user documentation (This Safety 

Manual and Technical manual) in regard to all relevant 

functional safety aspects such as application of use, 

installation, operation, maintenance, proof tests, 

maximum ratings, environmental conditions, repair, etc;

2.  Selection of this equipment for use in safety functions 

and the installation, configuration overall validation, 

maintenance and repair shall only be carried out by 

competent personnel, observing all the manufacturer’s 

conditions and recommendations in the user 

documentation.

3.  All information associated with any field failures 

of this product should be collected under a 

dependability management process (e.g., IEC 

60300-3-2) and reported to the manufacturer.

4.  The unit should be tested at regular intervals to 

identify any malfunctions; in accordance with this 

safety manual.

Xenon beacon - SM87HXb & SM87XbT- drafT 1

   TM001 Issue J   February 2023   www.eaton.com

Содержание SM87HXB

Страница 1: ...Xenon beacon SM87HXB SM87XBT draft 1 Technical manual...

Страница 2: ...A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS...

Страница 3: ...ebruary 2023 www eaton com Contents 1 0 INTRODUCTION 1 2 0 INSTALLATION 1 General 1 Cable termination 1 3 0 OPERATION 1 4 0 MAINTENANCE 2 5 0 CERTIFICATION APPROVALS 2 IECEx units 2 ATEX units 2 6 0 F...

Страница 4: ...iv Xenon beacon SM87HXB SM87XBT English Xenon beacon SM87HXB SM87XBT draft 1 TM001 Issue J February 2023 www eaton com...

Страница 5: ...ce as they are not retained in the cover Gently twist the cover clockwise and anti clockwise whilst pulling it away from the base of the enclosure to gain access to the interior Cable termination shou...

Страница 6: ...70 C T80 C 55 C to 55 C T65 C 55 C to 40 C The IECEx certificate and product label carry the IECEx equipment protection level marking Gb Db Where Gb signifies suitability for use in a Zone 1 surface...

Страница 7: ...SIL2 Random hardware failures DD 0 DU 2 96E 07 SD 0 SU 8 12E 07 Probability of failure on demand PFDAVG 1 30E 03 Low Demand Mode SIL2 Probability of Dangerous failure on safety function PFH 2 96E 07...

Страница 8: ...4 Xenon beacon SM87HXB SM87XBT Contents 1 0 5 2 0 5 5 3 0 5 4 0 6 5 0 6 1 6 6 0 7 7 8 Xenon beacon SM87HXB SM87XBT draft 1 TM001 Issue J February 2023 www eaton com...

Страница 9: ...5 Xenon beacon SM87HXB SM87XBT 1 0 85 2 0 IEE NEMA IP 4 9 M8 Eaton 4 5 Eaton NEMA IP 4 0 15 Eaton 3 0 Xenon beacon SM87HXB SM87XBT draft 1 TM001 Issue J February 2023 www eaton com...

Страница 10: ...IIIC Tx Db IP66 IP67 SM87HXB 95 55 70 80 55 55 65 55 40 SM87XBT A 70 55 55 55 55 40 SM87XBT B 110 55 85 T9 5 55 70 80 55 55 65 55 40 lECEx lECEx Gb Db Gb 1 Db 21 EN60079 0 EN60079 1 EN60079 31 EX d B...

Страница 11: ...40 11 2 GD II 2 1 G D 1180 94 9 6 0 SM87HXB 20 10 SM87HXB SM87HXB IEC 61508 UL FMEDA SM87HXB IEC 61508 2 8760 1 SM87HXB SM87HXB HFT 0 SFF 73 MTTR 8 SIL2 DD 0 DU 2 96E 07 SD 0 SU 8 12E 07 PFDcp 1 30E...

Страница 12: ...8 Xenon beacon SM87HXB SM87XBT 1 2 3 IEC 60300 3 2 4 Xenon beacon SM87HXB SM87XBT draft 1 TM001 Issue J February 2023 www eaton com...

Страница 13: ...es c bles 10 3 0 FONCTIONNEMENT 10 4 0 ENTRETIEN 11 5 0 CERTIFICATION HOMOLOGATIONS 11 Unit s IECEx 11 Unit s ATEX 12 6 0 S CURIT FONCTIONNELLE 12 Introduction 12 valuation de s curit fonctionnelle 12...

Страница 14: ...ccessible et s r dans la mesure o elles ne sont pas retenues l int rieur du couvercle Tournez doucement le couvercle de gauche droite tout en l loignant de la base du bo tier afin d acc der l int rieu...

Страница 15: ...que appareils en inox PX99900233 Assemblage de composants lectroniques 110 Vca 60 fpm PX99900094 Assemblage de composants lectroniques 240 Vca 60 fpm PX99900121 Assemblage de composants lectroniques 2...

Страница 16: ...nctionner avec une tol rance sur la tension d alimentation de 20 des versions CA de la balise sont con ues pour fonction ner avec une tol rance de la tension d alimentation de 10 Les versions de la ba...

Страница 17: ...ux maximum les conditions environnementales les r parations etc 2 Le choix de cet quipement en vue d une utilisation de ses fonctions de s curit ainsi que son installation sa configuration sa validati...

Страница 18: ...ss 15 3 0 BETRIEB 15 4 0 INSTANDHALTUNG 16 5 0 ZERTIFIZIERUNG GENEHMIGUNGEN 16 Iecex einheiten 16 ATEX Einheiten 17 6 0 FUNKTIONSSICHERHEIT 17 Einf hrung 17 Bewertung der funktionalen sicherheit 17 Be...

Страница 19: ...die Schrauben sicher und leicht erreichbar auf da sie nicht im Deckel verbleiben Um das Ger teinnere freizulegen drehen Sie den Deckel vorsichtig im Uhrzeigersinn und gegen den Uhrzeigersinn und ziehe...

Страница 20: ...99900094 Elektronik Baugruppe 240 VAC 60 fpm PX99900121 Elektronik Baugruppe 24 VDC 60 fpm PX99900099 Xenon Ersatzr hre PX99900122 Schraube fur Abdeckung Edelstahl 4 Stuck erforderlich PX99900584 Schr...

Страница 21: ...er Leuchte wurden so konzipiert dass sie mit einer Versorgungsspannungstoleranz von 20 funktionieren Die Wechselstromversionen der Leuchte funktionieren mit einer Versorgungsspannungstoleranz von 10 D...

Страница 22: ...shandbuch und das technische Handbuch zu halten 2 Die Wahl dieses Ger ts f r die Verwendung in Sicherheitsfunktionen sowie die Installation Konfiguration Gesamtvalidierung Wartung und Reparatur d rfen...

Страница 23: ...nal 20 3 0 FUNCIONAMIENTO 20 4 0 MANTENIMIENTO 21 5 0 CERTIFICACI N APROBACIONES 21 Unidades IECEx 21 Unidades ATEX 22 6 0 SEGURIDAD FUNCIONAL 22 Introducci n 22 Evaluaci n de seguridad funcional 22 C...

Страница 24: ...hexagonal A F mientras sostiene la tapa sobre la base Guarde los tornillos en un lugar seguro y accesible ya que no se mantienen en la tapa Gire suavemente la tapa en sentido horario y antihorario mi...

Страница 25: ...n sus requisitos 5 0 Certificaci n aprobaciones Unidades IECEx Certificadas con IEC 60079 0 IEC 60079 1 e IEC 60079 31 Unidad Ex d N de certificaci n IEC IECEx BAS 09 0059 Ex d IIC Tx Tamb Gb Ex tb II...

Страница 26: ...as para funcionar en una tolerancia de tensi n de suministro de 20 mientras que las versiones de CA del faro est n dise adas para funcionar en una tolerancia de tensi n de suministro de 10 Las version...

Страница 27: ...s m ximos las condicio nes medioambientales las reparaciones etc 2 Solo el personal competente deber llevar a cabo la selecci n del equipo que vaya a utilizarse en las funciones de seguridad la instal...

Страница 28: ...dos cabos 25 3 0 FUNCIONAMENTO 25 4 0 MANUTEN O 26 5 0 CERTIFICA O APPROVA ES 26 Unidades INMETRO 26 Unidades IECEx 26 Unidades ATEX 27 6 0 SEGURAN A FUNCIONAL 27 Introdu o 27 Avalia o da seguran a fu...

Страница 29: ...mm que fixam a tampa na base Conserve os parafusos em um local seguro e acess vel visto que n o permanecem retidos na tampa Gire delicadamente a tampa no sentido hor rio ou anti hor rio enquanto puxa...

Страница 30: ...Errata 1 2011 ABNT NBR IEC 60079 1 2009 Errata 1 2011 ABNT NBR IEC 60079 31 2011 Programa de certifica o ou Portaria Portaria no 179 de 18 de maio de 2010 do INMETRO Classe de temperatura Tx M xima t...

Страница 31: ...o Sinalizador s o projetadas para funcionar com uma toler ncia de tens o de alimenta o de 20 as vers es CA do Sinalizador s o projetadas para funcionar com uma toler ncia de tens o de alimenta o de 10...

Страница 32: ...manuten o maximas as condicoes ambientais reparos etc 2 A sele o deste equipamento para uso em fun es de seguran a e a instala o a configura o a valida o total a manuten o e os reparos ser o realizad...

Страница 33: ...29 Xenon beacon SM87HXB SM87XBT Portugu s Brasileiro Xenon beacon SM87HXB SM87XBT draft 1 TM001 Issue J February 2023 www eaton com...

Страница 34: ...ion contained in this document and to prices are reserved so are errors and omissions Only order confirmations and technical documentation by Eaton is binding Photos and pictures also do not warrant a...

Отзывы: