background image

2

Instruction Booklet 

IB48083

Effective August 2014

Vacuum interrupter replacement 

SLN018, SL12, SL15, and SJ contactors  

  

EATON

 www.eaton.com

4. 

Remove control transformer primary fuses  

(Classic Ampgard only).

5. 

Remove the hollow screw above each interrupter.

6. 

Remove the bottle nuts from the top stems, using a screwdriver 

as shown in 

Figure 3

. Set aside the screws, nuts, and washers.

Figure 3. 

7. 

Remove the two 5/16-inch bolts attaching each bottle  

subassembly. Set bolts aside.

8. 

Withdraw the interrupter subassemblies from the contactor  

chassis, pulling the bottom end out first so that the top stud 

clears the rear frame of the chassis. The contact springs are 

loose at this point and should be captured and stored. The bottle 

subassembly consists of the interrupter, shunt, and related  

hardware. See 

Figure 1

.

9. 

Remove the old pivot plate from the crossbar. Retain hardware.

10. 

Loosen and remove the bottle bolt that holds the copper conduc-

tor to the bottom of the interrupter. Retain the shim from under 

the copper conductor and the copper spacer. 

 CAUTION

AT NO TIME DURING THE INSTALLATION OF THE NEW INTERRUPTER 

SHOULD TORQUE BE APPLIED TO THE MOVING END OF THE INTERRUPTER. 

INTERNAL DAMAGE MAY RESULT IF TORQUE IS APPLIED. THE USED 

INTERRUPTERS SHOULD BE DESTROYED. DESTROYING THE INTERRUPTERS 

WILL ENSURE THAT THEY ARE NOT LATER CONSIDERED NEW AND 

INSTALLED IN ANOTHER CONTACTOR.

11. 

Install the new pivot plate (provided with the new interrupter kit) 

on the crossbar.

12. 

Fasten the previously removed copper conductor to the new 

interrupter with the shim between the mold frame and the  

copper conductor. The bottle spacer is installed between the 

interrupter and the copper conductor. Do not tighten the bolt  

at this time.

13. 

Preset the shunt by bending the free end in a smooth curve to 

touch the stud, then release.

14. 

Install contact springs and cups onto the top stems, with cup on 

top, flange down. See 

Figure 4

.

Figure 4. 

15. Insert bottle subassemblies into chassis, putting top end in  

first and guiding the bottle stud into the slot in the pivot plate. 

Check to confirm that the spring and cup are between the  

interrupter and the crossbar.

16. 

Bolt the subassembly to the chassis, using the 5/16-inch bolts, 

two per pole.

17. 

Align the interrupter on the copper conductor (the bottle bolt is 

loose) until the stud does not rub or touch the slot in the hole  

in the pivot plate. Tighten the bottle bolt. See 

Figure 3

. Check 

alignment again to make sure it was maintained while tightening.

18. 

Attach shunts to the line side conductor.

19. 

Recheck to make sure that the bottle studs remain clear of the 

pivot plate. In particular, make certain that the shunts have a 

slight bow downward (from 

Step 12

) and do not push the bottle 

studs against the pivot plate. If they do touch the pivot plate, 

loosen the shunts from the line side conductor and repeat  

Step 12

 before refastening.

20. 

Close the contactor by applying rated voltage from an isolated 

power source, using adequate care against electrical shock. 

21. 

Install two bottle nuts, plus the two flat washers previously 

removed, onto the center pole bottle stud. Both bottle nuts must 

have their threaded flanges facing UP.