Instruction Leaflet 

IL01301008E

Effective June 2015

Installation and removal instructions for Series NRX 

undervoltage release, shunt trip, and overcurrent 

trip switch in left accessory tray 

EATON

 www.eaton.com

Accessory 

locking tab

ST

Figure 11. Step 5 (RF frame shown)

Step 6e: 

Route the two secondary leads behind the first molded  

tab, down under a second molded tab, and out the end of the 

accessory tray.

Molded tab 1

Molded tab 2

ST

Figure 12. Step 6 (NF frame shown)

Molded tab 1

Molded tab 2

ST

Figure 13. Step 6 (RF frame shown)

Step 7e: 

If there is another UVR or ST to install in the other available 

space of the left accessory tray, install it by repeating 

Step 4

 and 

Step 5

.

Step 8e: 

Carefully route the secondary leads of the second installed 

accessory by following the same routing path and using the same 

molded tabs as the first installed accessory from 

Step 6

.

UVR

ST

Figure 14. Step 8 (NF frame shown)

UVR

ST

Figure 15. Step 8 (RF frame shown) 

Step 9e: 

The left accessory tray should look as shown in 

Figure 15

 

with two accessories installed and secondary wires properly routed.

Step 10e: 

Place the left accessory tray with the installed UVR and/

or ST accessories back in its original position. Be careful not to bind 

secondary wires or connector plugs.

UVR

ST

Figure 16. Step 10 (NF frame shown)

Содержание Series NRX

Страница 1: ...OSITION 4 ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO THE OFF POSITION AND MECHANISM SPRINGS DISCHARGED FAILURE TO FOLLOW THESE STEPS FOR ALL PROCEDURES DESCRIBED IN THIS INSTRUCTION LEAFLET COULD RESU...

Страница 2: ...dication when a circuit breaker trips as a result of the trip unit reacting to an overcurrent condition An electrical indication will not occur unless a standard or interlocking Trip Indicator is inst...

Страница 3: ...power consumption VA Opening time ms 24 DC 20 26 8 14 425 2 50 32 DC 27 35 11 19 N A 50 48 DC 41 53 17 29 750 3 50 60 DC 51 66 21 36 825 4 50 110 127 50 60 Hz 94 140 44 66 1150 8 50 110 125 DC 94 138...

Страница 4: ...for RF frame of side clearance is required on an installed fixed breaker for tray removal Figure 6 Step 3 NF frame shown Thumb tab Figure 7 Step 3 RF frame shown Note N The shunt trip ST is intended...

Страница 5: ...is another UVR or ST to install in the other available space of the left accessory tray install it by repeating Step 4 and Step 5 Step 8 Carefully route the secondary leads of the second installed acc...

Страница 6: ...ractices Step 13 Replace the front cover and secure it in place with the four mounting screws previously removed in Step 1 Section 3 Removal of undervoltage release and or shunt trip in left accessory...

Страница 7: ...Step 6 Repeat Step 4 and Step 5 if the other accessory is also to be removed Step 7 If the tray will have a new ST and or UVR installed follow Step 4 through Step 13 of Section 2 If not just complete...

Страница 8: ...ndary wires or connector plugs Figure 28 Step 4 NF frame shown Trip unit interlock plate Figure 29 Step 4 RF frame shown Note N The proper routing of leads will prevent the wires from being pinched by...

Страница 9: ...of the NF frame tray and slide it to the left as shown for removal For the RF frame tray press the thumb tab down and slide the tray to the left for removal Note N A minimum of 2 00 inches 50 8 mm fo...

Страница 10: ...zing two release tabs together with small needle nose pliers and pulling out Figure 37 Keyed connector Tagged leads Figure 36 Leads and connectors Release tabs Figure 37 Connector plug removal Fixed b...

Страница 11: ...e terminal block is removed the accessory connector plug can be unplugged from the bottom of the terminal block Refer to Item 2 and Figure 37 under the heading General information in this section for...

Страница 12: ...leads 8 and 9 for OT2 Or if an Eaton approved trip unit tester is available perform the following steps with the Accessory Tray installed in the circuit breaker 1 Ensure that the trip indicator is de...

Страница 13: ...HSCH DEN F HREN m WARNUNG BEACHTEN SIE BEI INSTANDHALTUNGSMASSNAHMEN AN DIESEM GER T ALLE IN DIESER IL UND AUF DEM PRODUKT SELBST AUFGEF HRTEN HINWEISE DIE F NF SICHERHEITSREGELN SIND EINZUHALTEN FREI...

Страница 14: ...st mit Alarmton zeigt elektronisch an wenn ein Leistungsschalter aufgrund der Reaktion der Ausl seelektronik bei einer berlast ausl st Eine manuelle Ausl sung oder eine Ausl sung durch den Arbeitsstr...

Страница 15: ...zeit des Leistungs schalters ms 24 DC 20 26 8 14 425 2 50 32 DC 27 35 11 19 N A 50 48 DC 41 53 17 29 750 3 50 60 DC 51 66 21 36 825 4 50 110 127 50 60 Hz 94 140 44 66 1150 8 50 110 125 DC 94 138 44 66...

Страница 16: ...er Baugr e RF 77 mm Abbildung 6 Schritt 3 IZMX16 Abbildung 7 Entriegelungshebel Schritt 3 IZMX40 Hinweis H Der Arbeitsstromausl ser ST wird auf den linken Steckplatz geklipst Der 2te Arbeitsstromausl...

Страница 17: ...6 IZMX40 Schritt 7 Um einen weiteren Unterspannungs oder Arbeitsstromausl ser in den linken Zubeh reinschub einzubauen wiederholen Sie die Schritte 4 und 5 Schritt 8 F hren Sie die Kabel wie in Schrit...

Страница 18: ...hl ssen wie in Abschnitt 6 ausgef hrt Nutzen Sie geeignete Kabelbinder wenn n tig Schritt 13 Bauen Sie die Frontabdeckung wieder an Abschnitt 3 Entfernen der Unterspannung sausl ser und Arbeitsstromau...

Страница 19: ...die Schritte 4 und 5 um weitere Unterspannungs oder Arbeitsstromausl ser zu entfernen Schritt 7 Falls nun neue Arbeitsstromausl ser und oder Unterspannungsausl ser eingebaut werden sollen f hren Sie...

Страница 20: ...ieder in den Schalter Achten Sie auf die Leitungsf hrung Abbildung 28 Schritt 4 IZMX16 Abbildung 29 Verriegelung der Ausl seelektronik Schritt 4 IZMX40 Hinweis H Sollten die Leitungen nicht ordnungsge...

Страница 21: ...ngsschaltern der Baugr e RF hat einen Hebel der zum Entriegeln bet tigt werden muss Hinweis H Um den Zubeh reinschub entfernen zu k nnen werden bei einem Festeinbauschalter der Baugr e NF mindestens 5...

Страница 22: ...lteklemmen mit einer kleinen Zange zusammengedr ckt werden und der Stecker herausgezogen wird siehe Abbildung 37 Abbildung 36 Verbindungsstecker Gekennzeichnete Leitungen Leitungen und Verbindungsstec...

Страница 23: ...OT1M UV2 ST2 ST1 UV1 OT1C OT1B OT2C ALMC G1 SGF2 24V CMM1 Abbildung 42 Schritt 1 Schritt 2 Stecken Sie den Verbindungsstecker in die entsprechend markierte Position Abbildung 43 1 2 Schritt 2 m WICHTI...

Страница 24: ...fer 2 Setzen Sie den Zubeh reinschub wieder ein und stellen Sie sicher dass der Ausgel stmelder eingedr ckt ist Pr fen Sie nun die Kontinuit t zwischen den Steuerleitungen 5 und 7 f r OT1 sowie 8 und...

Отзывы: