Specifications
44
Eaton Remote Power Panel (RPP) User’s Guide 164202125—Rev 5
www.eaton.com/powerquality
Table 19. EMS Meter
Calibration
Fully calibrated at the factory
Clock
Real Time Clock (RTC) with one-second resolution, automatic leap year adjustment, and one month backup time
Display
Backlit LCD panel with 8 lines by 40 characters (approximately 64 x 240 pixels), 4 LED indicators, and 5 pushbuttons
Table 20. Environmental and Safety
Operating Temperature
0
C to 40
C (32
F to 104
F) without derating. The recommended operating temperature is 25°C (77°F
Storage Temperature
-25°C to 60°C (-13°F to 140°F)
Relative Humidity
10% to
95% maximum noncondensing
Operating Altitude
Maximum 1500m (5000 ft) at 40°C without derating
Heat Dissipation
3412 BTU/hr maximum
Audible Noise
Less than 45 dBA at 1.5m (5 ft)
EMI Suppression
Meets FCC Regulation 47, Part 15, for class A devices
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without damage
and with no disturbance or adverse effect to the critical load.
Agency Markings
US Domestic/Canadian: Marking – cULus
Standard – UL60950-1:2007, CAN/CSA-C22.2 No. 60950-1-07
Table 21. SPD
Technology
Thermally Protected Metal Oxide Varistors (TPMOVs)
Peak Surge Current
100 kA/phase (Non-EMS monitored)
100 kA/phase (EMS monitored)
200 kA/phase (EMS monitored)
Nominal Discharge Current
20kA
Indicators (for Non-EMS
monitored model only)
Three high intensity LED indicator for each phase protected
Noise Attenuation (for EMS
monitored models only)
EMI/RFI filtering, up to 50 dB noise attenuation from 10 kHz to 100 MHz
Safety Conformance
UL 1449 3rd Edition
Relay Contact (for EMS
monitored models only)
Form C relay contact monitored by Eaton EMS