Eaton Corporation Page 52 Ver 1.1
Configuration for the AC Wiring:
A)
After the DC wiring connection is finished, start to dash an opening hole
for the AC cabling, and insert the conduit and tighten with the pipe end
fitting.
Figure 7.2.2.1: Install a conduit on an open hole
B)
Ensure the AC utility system that selected is able to use with Eaton
grid-connected PV Inverter. After utility system confirmed, to select the
correct setting of utility configuration setting DIP switch with the
following instructions that mentioned in section 7.2.1 before to start
procedures for the AC connection.
IMPORTANT
For the 3800W down powered mode, it is important to adjust the
setting of the Utility configuration setting by turning on the number
4 Dip switch.
When the number 4 DIP switch is turned
on, the output power is limited at 3.8kW.
This is only available with the PV240
model. It is necessary to change all the
name plates if this change conducted.