UPS INSTALLATION PLAN AND UNPACKING
Eaton
Power Xpert 9395P-600 (380V-600V) UPS Installation and Operation Manual
S
P-164000710 Rev 1
www.eaton.com/powerquality
3-5
The UPS 415V/400V/380V ventilation requirements are shown in Table 3‐5.
Table 3‐5. 415V/400V/380V Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Heat Rejection
kW (1000 BTU/hr)
Ventilation Required for Cooling Air Exhaust
Eaton 9395P-600/550
(CSS or IOM)
550 kVA
550 kW
415/415
400/400
380/380
22.7 (77.42)
Approximately 3050 liter/sec (6500 CFM)
Eaton 9395P-600/500
(CSS or IOM)
500 kVA
500 kW
415/415
400/400
380/380
20.6 (70.38)
Eaton 9395P-600/450
(CSS or IOM)
450 kVA
450 kW
415/415
400/400
380/380
18.6 (63.35)
Eaton 9395P-600/400
(CSS or IOM)
400 kVA
400 kW
415/415
400/400
380/380
16.5 (56.31)
Eaton 9395P-600/300
(CSS or IOM)
300 kVA
300 kW
415/415
400/400
380/380
12.4 (42.23)
Approximately 1700 liter/sec (3600 CFM)
With field installed FI-UPM:
Approximately 3050 liter/sec (6500 CFM)
Eaton 9395P-600/275
(CSS or IOM)
275 kVA
275 kW
415/415
400/400
380/380
11.3 (38.71)
Eaton 9395P-600/250
(CSS or IOM)
250 kVA
250 kW
415/415
400/400
380/380
10.3 (35.19)
Eaton 9395P-600/225
(CSS or IOM)
225 kVA
225 kW
415/415
400/400
380/380
9.3 (31.67)
Eaton 9395P-600/200
(CSS or IOM)
200 kVA
200 kW
415/415
400/400
380/380
8.2 (28.15)
NOTE
CSS = Continuous Static Switch; IOM = Input Output Module
3.2.3
Standard 380V, 400V, 415V, and 480V Model Configurations
Front view illustrations of configuration dimensions and Center of Gravity
measurements are provided for each non-600V model configuration (380V, 400V, 415,
and 480V). Figure 3‐13 provides side view illustrations of dimensions and side view
Center of Gravity measurements that apply for all configurations.
S
Single UPM:
ISBM and 1 x UPM section (shipped joined on a single pallet).
See Figure 3‐1 and Figure 3‐2.
S
Single UPM PLUS 1 UPM:
ISBM and 1 x UPM section (shipped joined on a single
pallet), plus 1 Field Installed FI-UPM (shipped separately to be added to
configuration later). See Figure 3‐3 and Figure 3‐4.
S
TWO UPM:
ISBM and 2 x UPM section (shipped joined on a single pallet). See
S
TWO UPM PLUS 1 UPM:
ISBM and 2 Factory Installed UPMs (shipped joined on a
single pallet), plus 1 Field Installed FI-UPM (shipped separately to be added to
configuration later). See Figure 3‐7 and Figure 3‐8.