Step 3
Mount the conduit fittings
⑧⑨
on the NEMA 1 kit main
frame
⑦
. Then insert the hooks on bottom plate into the
corresponding rectangular openings on drive bottom surface.
Table 18. Conduit fitting for wires.
Conduit fitting for
control wires
Conduit fitting for
power wires
FR1
0.5 inch, 2 pcs.
0.5 inch, 3 pcs.
FR2
0.5 inch, 2 pcs.
0.75 inch, 3 pcs.
FR3
0.5 inch, 2 pcs.
0.75 inch, 3 pcs.
FR4
0.5 inch, 2 pcs.
1.0 inch, 3 pcs.
Step 4
Power wiring for EMI version drive:
1. Run input cable (including three line wires and one
input grounding wire) through conduit fitting and input
magnetic core
⑩
, then connect to L1/L2/L3 terminals,
leave the input grounding wire
⑪
unconnected. Tie the
input magnetic core to the input wires with a cable tie
(See A).
2. Run the output cable (including three motor wires and
one output grounding wire) through conduit fitting
and EMC grounding clamp
⑭
. Run the three motor
wires without the output grounding wire through the
output magnetic core
⑫
. Connect the motor wires to
U/V/W terminals. Leave the output grounding wire
⑬
unconnected. Tie output magnetic core to the output
wires with a cable tie. Use the EMC grounding clamp
⑭
and two screws
⑮
to fix output cable shielding layer
(See B).
Power wiring for non-EMI version drive:
Run input cable (including three line wires and one input
grounding wire) through conduit fitting. Connect to L1/L2/L3
terminals. Leave the input grounding wire
⑪
unconnected
3. Run the output cable (including three motor wires and
one output grounding wire) through conduit fitting and
EMC grounding clamp
⑭
. Connect the motor wires to
U/V/W terminals. Leave the output grounding wire
⑬
unconnected. Use the EMC grounding clamp
⑭
and two
screws
⑮
to fix output cable shielding layer.
Control wiring:
1. Run control wires (RJ45, ethernet, I/O, STO, relay, etc.)
through control wire conduit fittings
⑨
and connect to
corresponding terminals or connectors.
Hooks
Conduit fittings for power wires
⑧
NEMA1 kit main frame
⑦
Conduit fittings for control wires
⑨
A
B
Output grounding wire
⑬
Output magnetic core
⑫
Input magnetic core
⑩
EMC grounding clamp
⑭
Screws
⑮
Input grounding wire
⑪