
26
Modbus TCP On-Board communications
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Example of the request to write single coil 2000 from Slave
device 18, the output value is 1.
Table 45. Request to write single coil
Item
Code
Description
Slave address
0x12
Function code
0x05
Output address High
0x07
Starting address 0x07D0 hex (= 2000)
Output address Low
0xD0
Output value High
0xFF
Output value 0xFF00 hex (= 65280)
Output value Low
0x00
Note. Output value is 0x0000 or 0xFF00
CRC High
0x8E
CRC Low
0x14
Example of the request to write single register 2000 from
Slave device 18, the output value is 5.
Table 46. Request to write single register
Item
Code
Description
Slave address
0x12
Function code
0x06
Output address High
0x07
Starting address 0x07D0 hex (= 2000)
Output address Low
0xD0
Output value High
0x00
Output value 0x0005 hex (= 5)
Output value Low
0x05
CRC High
0x4B
CRC Low
0xE7
Example of Write coils 19–28 from Slave device 18.
Table 47. Write coils 19–28
Item
Code
Description
Slave Address
0x12
Function code
0x0F
Starting Address High
0x00
Starting Address 0x0013 (= 19)
Starting Address Low
0x13
Quantity of Outputs High 0x00
Quantity of Outputs 0x000A (= 10)
Quantity of Outputs Low 0x0A
Bye Count
0x02
Outputs Value High
0xCD
Outputs Value Low
0x01
CRC High
0xAB
CRC Low
0xFB
ote:
N
The binary outputs in the previous example
correspond to the outputs in the following way.
Table 48. Binary bits and corresponding outputs
Bit
1
1
0
0
1
1
0
1
0
0
0
0
0
0
0
1
Output
26 25 24 23 22 21 20 19 — — — — — — 28 27
Example of write Holding registers 2000–2001 from Slave
device 18.
Table 49. Write holding registers
Item
Code
Description
Slave Address
0x12
Function code
0x10
Starting Address High
0x07
Starting Address 0x07D0 (= 2000)
Starting Address Low
0xD0
Quantity of Outputs High 0x00
Quantity of Outputs 0x0002 (= 2)
Quantity of Outputs Low 0x02
Bye Count
0x04
Outputs Value High
0x00
Outputs Value Low
0x01
Outputs Value High
0x00
Outputs Value Low
0x02
CRC High
0x53
CRC Low
0x46
Modbus registers
The variables and fault codes as well as the parameters can
be read and written from Modbus. The parameter addresses
are determined in the application. Every parameter and actual
value have been given an ID number in the application. The
ID numbering of the parameter as well as the parameter
ranges and steps can be found in the application manual in
question. The parameter value shall be given without decimals.
All values can be read with function codes 3 and 4 (all
registers are 3X and 4X reference). Modbus registers are
mapped to drive IDs as follows.
Table 50. Index table
ID
Modbus register
Group
R/W
1–98
40001–40098
(30001–30098)
Actual Values
1/1
100
40099 (30099)
Fault Code
1/1
101–1999
40101–41999
(30101–31999)
Parameters
1/1
2004–2011
42004–42011
(32004–32011)
Process Data In
1/1
2104–2111
42104–42111
(32104–32111)
Process Data Out
1/1