77
BACnet MS/TP—On-Board communication
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Analog value object instance summary
The following table summarizes the Analog Value Objects supported.
Table 100. AnalNg value Nbjeco insoance summary
Instance ID
Object name
Description
Units
Preset value
access
AV0
Frequency set point
Frequency set point
Hz
R
AV1
Output frequency
Output frequency
Hz
R
AV2
Motor speed
Motor speed
Rpm
R
AV3
Motor load
Motor shaft power
Percent
R
AV4
Megawatt hours total
Megawatt hour counter (total)
MWh
R
AV5
Motor current
Motor current
Amps
R
AV6
Dc link voltage
Dc link voltage
Volts
R
AV7
Motor voltage
Motor voltage
Volts
R
AV8
Unit temperature
Heatsink temperature
°C
R
AV9
Motor torque
Motor torque
Percent
R
AV10
Operating days
Operating days (resettable)
Day
R
AV11
Operating hours
Operating hours (resettable)
Hour
R
AV12
Torque reference
Torque reference
Percent
R
AV13
Motor temperature
Motor temperature
Percent
R
AV14
Active fault code
Latest active fault code
No Units
R
AV15
Speed reference
Motor speed reference from network
%
C
AV16
Current limit
Current limit
Amps
W
AV17
Min frequency
Minimum frequency
Hz
W
AV18
Maximum frequency
Maximum frequency
Hz
W
AV19
Accel time 1
Acceleration time
seconds
W
AV20
Decel time 1
Deceleration time
seconds
W
AV21
Anyparam id
Parameter id number to be accessed
No Units
W
AV22
Anyparam value
Value of parameter defined by av21
No Units
W
AV23
Analog input 1
Analog input 1
Volts
R
AV24
Analog input 2
Analog input 2
Volts
R
AV25
Analog output 1
Analog output 1
Volts
R
AV26
Analog output 2
Analog output 2
Volts
R
Noee:
N
For Present Value Access Types, R = Read-only,
W = Writeable, C = Commandable. Commandable
values support priority arrays and relinquish defaults.