PROFIBUS-DP external communication cards
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Below is various defined control word (STW1) command.
Table 118. Control word (STW1) message examples
SN
Control
word
(STW1)
Control word description (STW1)
Comment
1
0x0400
Set PLC Control
PLC Control should be set in MCU
2
0x0000
Clear PLC Control
PLC Control should be reset in MCU
3
0x040F
Run Command without RFG
Motor Off as no RAMP Generator
4
0x0407
Clear Run Command
Motor Off as earlier
5
0x041F
Run Command with RFG and without Set point
Motor Off as no Set point Generator
6
0x0407
Clear Run Command
Motor Off as earlier
7
0x047F
Run Command with RFG and with Set point
Motor ON with RFG
8
0x0407
Clear Run Command
Motor Off as earlier
9
0x047F
Run Command with RFG and with Set point
Motor ON with RFG
10
0x045F
Set Freeze of Ramp
Motor ON with Ramp Freeze
11
0x047F
Clear Freeze of Ramp
Motor ON with Following Ramp Timing
12
0x047E
OFF 1 Command
Motor Off with RFG
13
0x047F
Run Command with RFG and with Set point
Motor ON with RFG
14
0x047D
OFF 2 Command (Coast Stop)
Motor Off with Coast
15
0x047F
Run Command with RFG and with Set point
Motor ON with RFG
16
0x047B
OFF 3 Command (Quick Stop)
Motor Off with 0 DECEL Time
17
0x047F
Run Command with RFG and with Set point
Motor ON with RFG
18
0x0477
Disable Operation
Motor Off with Coast
19
0x057F
Run Command with RFG and with Set point At Jog Speed
Motor ON at Jog Speed
20
0x0477
Disable Operation
Motor Off with Coast
21
0x0480
Fault Reset bit
Fault should get reset