Appendix B—Installation Guidelines
DG1 Series VFD
MN040002EN—March 2014
www.eaton.com
47
Table 30. International Cable and Fuse Sizes—208 Vac to 240 Vac Ratings
Notes
1
Line and motor cable size is selected according to IEC60364–5–52:2009 Table B.52.4 for copper conductor with PVC insulation with a wiring condition of ambient
temperature 30°C in air and an installation method of “B2” (cables in conduit and cable trunking systems). For other wiring conditions, please refer to the
standard of IEC60364–5–52:2009 for suitable cable sizes.
2
Earthing conductor size is determined by the cross–sectional area of phase conductors according to IEC/EN61800–5–1:2007 Table 5. So if phase conductor size
is changed, earthing conductor size should also be changed accordingly.
3
If power cubes or bypass are used, a Class gG/gL fuse is recommended.
4
Available in 2015.
Frame
Size
Amp
Suffix
208V
Input
Current
(CT/I
H
)
208V
Input
Current
(VT/I
L
)
Current
(CT/I
H
)
at 50°C
Current
(VT/I
L
)
at 40°C
Fuse
Rating
(gG/gL)
Mains and
Motor Cable
Cu (mm
2
)
Terminal Cable Size
Main Terminal
Cu (mm
2
)
Earth Terminal
Cu (mm
2
)
FR1
3D7
3.2
4.4
3.7
4.8
6
3*1.5+1.5
0.2–6 solid or
0.2–4 stranded
0.75–6
4D8
4.4 6.1 4.8
6.6
10
3*1.5+1.5
0.2–6
solid
or
0.2–4 stranded
0.75–6
6D6
6.1 7.2 6.6
7.8
16
3*1.5+1.5
0.2–6
solid
or
0.2–4 stranded
0.75–6
7D8
7.2
10.2
7.8
11
16
3*1.5+1.5
0.2–6 solid or
0.2–4 stranded
0.75–6
011
10.2 11.6 11
12.5
16
3*1.5+1.5
0.2–6
solid
or
0.2–4 stranded
0.75–6
FR2
012
10.2 16.3 12.5
17.5
20
3*4+4
0.5–16
4–16
017
16.2 23.2
17.5
25
32
3*4+4
0.5–16
4–16
025
23.1 29
25
31
32
3*6+6
0.5–16
4–16
FR3
031
28.7 44.2
31
48
50
3*16+16
16–35
2.5–25
048
44.4 56
48
61
63
3*16+16
16–35
2.5–25
FR4
061
56.4 64.6 61
75
80
3*25+16
16–50
6–50
075
69.4 78
75
88
100
3*35+16
16–50
6–50
088
81.4 94.3
88
114
125
3*50+25
16–50
6–50
FR5
114
105.5 129
114
143
160
3*70+35
50–185
10–120
143
132.3 157
143
170
200
3*95+50
50–185
10–120
170
157.3 189
170
211
250
3*150+95
50–185
10–120
FR6
211
195.2
4
211
261
4
4
4
4
261
241.4
4
261
312
4
4
4
4