background image

Figure 7. Voltage Transient

+208 Volts rms

-208 Volts rms

0

Amplitude is
typically double
the line voltage
or greater and
less than one
cycle in duration.

+208 Volts rms

-208 Volts rms

+208 Volts rms

-208 Volts rms

Swell

Swell

Normal

Normal

Sag

Sag

PXL Series Installation
and Operation Manual

Instruction Manual

Page 8 Effective: January 2006

4.3 Common Causes of SPD
Problems

4.3.1 Voltage Regulation

4.3.2 Temporary Overvoltage
(TOV)

SPDs are applied to electrical systems to
mitigate surges, transients, impulse or
spikes. By definition, surges are random
high magnitude short-term voltage
disturbances. These high impulses can
cause havoc to electronic devices if no
protection is applied.

- Voltage Transient. This

image represents a transient voltage
surge on the 60 Hz AC sine wave. The
transient is very short in duration but very
high in magnitude from the nominal AC
line voltage. Tests have shown that the
greater the amplitude of the surge
voltage, the greater the risk of damage
occurring to downstream electronic
systems. Additionally, voltage transients
originate from variety of sources,
externally form lightning and utility faults,
and internally generated from switching
loads, electronic power supplies, etc.

Problems associated with voltage
regulation are more commonly
understood since these events happen
over very long time periods. Voltage
surges should not be confused with
voltage regulation problems. By definition,
voltage surges occur in the microsecond
range and voltage regulation is defined as
having a duration of 1 cycle to many
cycles or even hours. Voltage regulation
can only damage an SPD if the voltage
rises near or above its MCOV (maximum
continues operating voltage).

Full detailed explanations can be found in
the IEEE (Institute of Electrical and
Electronics Engineers) publication often
referred to us as the “Emerald Book”.
TOV or swells are 60 Hz voltage events
that can occur from 1 cycle to a few
seconds. See Figure 10 - Line Voltage
Swells (TOV) and Sags. The normal AC
sine wave in reference to the swell and
sag clearly illustrates the difference in the
types of events. TVSS or SPDs are
devices that shunt surge events -
microseconds events. TOV will often last
for cycles and fail MOV-based SPDs.

See Figure 7

4.4 Troubleshooting

The PXL is a rugged suppression device.
In the unlikely case that the indicator
lights change status, audible alarm or
remote alarms are activated. First contact
our Application Engineers at (800) 809-
2772 (option 4, sub-option 2). They will
help determine the cause of your problem
and direct you to the warranty process if
applicable.

Figure 8. Line Voltage Swells (TOV) and Sags

4.4.1 PXL Power System
Troubleshooting Guide

Improper installation of the SPD at site is
the most common application problem.
Please follow these instructions carefully
for proper SPD operation.

Effective 01.06

IM 01005001E

information visit: www.eatonelectrical.com

Содержание Powerware PXL Series

Страница 1: ...Installation and Operation Manual for Powerware PXL Series Surge Protective Device IM 01005001E For more information visit www eatonelectrical com Effective 01 06 Instruction Manual IM01005001E...

Страница 2: ...Table of contents Description Page Section 1 Introduction 3 Section 2 Installation Procedure 3 Section 3 Operating Features 6 Section 4 Troubleshooting 7 Section 5 Warranty and Technical Assistance 15...

Страница 3: ...at hi pot testing not be performed on connected SPDs From the installers point of view it is also important that SPDs are not connected while performing a hi pot test since the SPD will always cause t...

Страница 4: ...e Twist and bind together all leads Route the wires such that their overall length is kept to a minimum This reduces line impedance and optimizes performance Strip the ends of the wires and terminate...

Страница 5: ...ge 5 Effective January 2006 SPD Figure 3 3 Phase Wye 4 Wire Ground PE Voltage Codes 208Y 480Y CPS Figure 2 3 Phase Delta 3 Wire Ground PE Voltage Codes 240D 480D SPD Figure 1 Single Phase Split Phase...

Страница 6: ...perating status each PXL is equipped with status indicator lights All units are equipped with integral fusing Should the SPD fail and create a short circuit the overcurrent will isolate the fault Thes...

Страница 7: ...form C relay monitoring contacts by switching the power and back Contact are rated up to 1A 220 VAC NO NC COM OFF ON Note Section 4 Troubleshooting 4 1 Life expectancy Note The PXL is not field repai...

Страница 8: ...e surges should not be confused with voltage regulation problems By definition voltage surges occur in the microsecond range and voltage regulation is defined as having a duration of 1 cycle to many c...

Страница 9: ...m All LEDs are green No alarms Normal operation 3 phase configuration NA Two green LEDs are ON Split phase configuration Normal operation NA 100KA All green LEDs are ON Alarm disabled LED ON Normal op...

Страница 10: ...and N G voltage should be less than 3 volts for 3 phase 4 wire system Lost Neutral Condition 2 Neutral conductor not connected or poor connection intermittent All LEDs are OFF buzzer OFF One or more r...

Страница 11: ...formation on the Premium display menu features All LEDs are green No alarms Normal operation 3 phase configuration NA VAN VBN 120 120 Two LEDs are green No alarms Normal operation split phase configur...

Страница 12: ...VAC VCA 208 81 208 Lost phase voltage No voltage on specified phase Confirm corresponding SPD phase connection terminals are connected Check breaker voltage Check panel voltage One or more red LEDs ON...

Страница 13: ...08 208 208 Internal fuse blown Measure terminal voltage with multimeter and if voltage is in spec then call Press DISABLE ALARM button on display United States support 1 800 809 2772 Australia support...

Страница 14: ...5 2 Premium Display Calibration Procedure Steps Shut OFF power to the unit Press and hold the STEP button Do NOT release arrow 2 Apply power to the unit The display will show first row second row Rel...

Страница 15: ...Y AS TO THE MERCHANT ABILITY FITNESS FOR PURPOSE SOLD DESCRIPTION QUALITY PRODUCTIVENESS OR ANY OTHER MATTER In no event shall Eaton Powerware be liable for special or consequential damages or for del...

Страница 16: ...2006 Eaton Corporation All Rights Reserved Printed in USA Publication No IM01005001E 1000 Cherrington Parkway Moon Township PA 15108 4312 USA Tel 1 800 525 2000 www eatonelectrical com...

Отзывы: