background image

Installation and Operation Manual for Powerware
PXL Series Surge Protective Device

IM 01005001E

For more information visit: www.eatonelectrical.com

Effective 01.06

Instruction Manual:

IM01005001E

Содержание Powerware PXL Series

Страница 1: ...Installation and Operation Manual for Powerware PXL Series Surge Protective Device IM 01005001E For more information visit www eatonelectrical com Effective 01 06 Instruction Manual IM01005001E...

Страница 2: ...Table of contents Description Page Section 1 Introduction 3 Section 2 Installation Procedure 3 Section 3 Operating Features 6 Section 4 Troubleshooting 7 Section 5 Warranty and Technical Assistance 15...

Страница 3: ...at hi pot testing not be performed on connected SPDs From the installers point of view it is also important that SPDs are not connected while performing a hi pot test since the SPD will always cause t...

Страница 4: ...e Twist and bind together all leads Route the wires such that their overall length is kept to a minimum This reduces line impedance and optimizes performance Strip the ends of the wires and terminate...

Страница 5: ...ge 5 Effective January 2006 SPD Figure 3 3 Phase Wye 4 Wire Ground PE Voltage Codes 208Y 480Y CPS Figure 2 3 Phase Delta 3 Wire Ground PE Voltage Codes 240D 480D SPD Figure 1 Single Phase Split Phase...

Страница 6: ...perating status each PXL is equipped with status indicator lights All units are equipped with integral fusing Should the SPD fail and create a short circuit the overcurrent will isolate the fault Thes...

Страница 7: ...form C relay monitoring contacts by switching the power and back Contact are rated up to 1A 220 VAC NO NC COM OFF ON Note Section 4 Troubleshooting 4 1 Life expectancy Note The PXL is not field repai...

Страница 8: ...e surges should not be confused with voltage regulation problems By definition voltage surges occur in the microsecond range and voltage regulation is defined as having a duration of 1 cycle to many c...

Страница 9: ...m All LEDs are green No alarms Normal operation 3 phase configuration NA Two green LEDs are ON Split phase configuration Normal operation NA 100KA All green LEDs are ON Alarm disabled LED ON Normal op...

Страница 10: ...and N G voltage should be less than 3 volts for 3 phase 4 wire system Lost Neutral Condition 2 Neutral conductor not connected or poor connection intermittent All LEDs are OFF buzzer OFF One or more r...

Страница 11: ...formation on the Premium display menu features All LEDs are green No alarms Normal operation 3 phase configuration NA VAN VBN 120 120 Two LEDs are green No alarms Normal operation split phase configur...

Страница 12: ...VAC VCA 208 81 208 Lost phase voltage No voltage on specified phase Confirm corresponding SPD phase connection terminals are connected Check breaker voltage Check panel voltage One or more red LEDs ON...

Страница 13: ...08 208 208 Internal fuse blown Measure terminal voltage with multimeter and if voltage is in spec then call Press DISABLE ALARM button on display United States support 1 800 809 2772 Australia support...

Страница 14: ...5 2 Premium Display Calibration Procedure Steps Shut OFF power to the unit Press and hold the STEP button Do NOT release arrow 2 Apply power to the unit The display will show first row second row Rel...

Страница 15: ...Y AS TO THE MERCHANT ABILITY FITNESS FOR PURPOSE SOLD DESCRIPTION QUALITY PRODUCTIVENESS OR ANY OTHER MATTER In no event shall Eaton Powerware be liable for special or consequential damages or for del...

Страница 16: ...2006 Eaton Corporation All Rights Reserved Printed in USA Publication No IM01005001E 1000 Cherrington Parkway Moon Township PA 15108 4312 USA Tel 1 800 525 2000 www eatonelectrical com...

Отзывы: