Eaton 9395 UPS (225–300 kVA) Single Feed Kit
S
164201722 Rev 2
www.eaton.com/powerquality
1
Eaton 9395 UPS (225–300 kVA) Single-Feed Kit Installation
NOTE
Refer to the applicable installation and operation manual supplied with the UPS during installation.
W
A
R
N
I
N
G
Installation should be performed only by qualified personnel.
To install the single-feed kit:
1.
If not already accomplished, remove one top screw and two bottom screws
securing the UPS left front panel (refer to the applicable Eaton 9395 UPS manual
for panel location). Lift the panel straight up to remove it from the panel hanger
bracket at the top of the cabinet.
2.
If not already accomplished,remove the screws securing the internal safety
shield panel and remove the panel to gain access to the rectifier and bypass input
terminals. Retain the hardware for later use.
3.
Using hardware from the single-feed kit (see Table 1), install the single-feed
jumper cables from the kit between the rectifier input terminals and the input
bypass input terminals (see Figure 1). Tighten the bolts to the torque values
listed in Table 2.
4.
Return to the applicable Eaton 9395 UPS manual to complete the wiring.
Table 1. Supplied Terminal Hardware
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Jumper Cable
N/A
6
Rectifier and Bypass Input
152602507
(wire kit with 6 cables)
Bolt, Grade 5
M12
45 mm
6
Rectifier and Bypass Input
180190078-113
Flat Washer
M12
12
Rectifier and Bypass Input
180500036-120
Conical Washer
M12
6
Rectifier and Bypass Input
180500037-120
Nut
M12
6
Rectifier and Bypass Input
180200001-07
Table 2. Single-Feed Power Cable Terminations
Terminal Function
Terminal
Function
Bus Landing
Tightening Torque
Nm (lb ft)
Bolt Size
Rectifier Input
E1
Phase A
1 – 1 bolt mounting
76 (56)
M12
E2
Phase B
1 – 1 bolt mounting
76 (56)
M12
E3
Phase C
1 – 1 bolt mounting
76 (56)
M12
Bypass Input
E6
Phase A
1 – 1 bolt mounting
76 (56)
M12
E7
Phase B
1 – 1 bolt mounting
76 (56)
M12
E8
Phase C
1 – 1 bolt mounting
76 (56)
M12