COMMUNICATION
EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
7−6
7.4.2
Install the Card
NOTE
See Figure 6-2 on page 6−3 for X−Slot communication bay locations.
To install the Powerware ConnectPDU Web/SNMP Card:
1.
Verify that the PDU is turned off and all power sources are removed. See
Chapter 6, PDU Operating Instructions," for shutdown instructions.
2.
Verify that both DIP switches on the card are set to the
0
(off) position (see
Figure 7-3. Verify DIP Switches
NOTE
If you are setting up the Powerware ConnectPDU Web/SNMP Card in a DHCP environment, set DIP
switch 2 to the
1
(on) position.
NOTE
If there is another card already installed with an attached communication cable, disconnect the
cable and then remove the card.
3.
To prevent electrostatic discharge (ESD), place one hand on a metal surface such
as the PDU cabinet frame.
4.
Slide the card into the open slot and secure with the screws.
5.
Connect an active Ethernet cable (supplied) to the Uplink Ethernet connector on
the Powerware ConnectPDU Web/SNMP Card.
6.
To configure the card locally using the supplied configuration cable, continue to
paragraph 7.4.3.
To configure the card remotely through a network using a Web browser or Telnet
(or similar) utility, refer to the
Powerware ConnectPDU Web/SNMP Card
User’s
Guide
PDF downloaded from powerware.com.